UPS INSTALLATION PLAN AND UNPACKING
EATON Powerware
®
 9395 UPS (650–825 kVA) Installation and Operation Manual  
S
  164201725 Rev 2 www.powerware.com
3−2
Table 3-1. UPS Cabinet Weights
Model
Section
Weight 
kg (lb)
Shipping
Installed
Powerware 9395−825/650
ISBM
1498 (3302)
1390 (3064)
UPM
1590 (3505)
1482 (3267)
Powerware 9395−825/750
ISBM
1498 (3302)
1390 (3064)
UPM
1590 (3505)
1482 (3267)
Powerware 9395−825/825
ISBM
1498 (3302)
1390 (3064)
UPM
1590 (3505)
1482 (3267)
The UPS cabinet uses forced air cooling to regulate internal component temperature.
Air inlets are in the front of the cabinet and outlets are in the top. Allow clearance in
front of and above each cabinet for proper air circulation. The clearances required
around the UPS cabinet are shown in Table 3-2.
Table 3-2. UPS Cabinet Clearances
From Top of Cabinet
457.2 mm (18") minimum clearance for ventilation
From Front of Cabinet
914.4 mm (36") working space
From Back of Cabinet
None Required
From Right Side of Cabinet
152.4 mm (6") working space
From Left Side of Cabinet
None Required
The basic environmental requirements for operation of the UPS are:
S
Ambient Temperature Range:
0–40°C (32–104°F)
S
Recommended Operating Range: 20–25°C (68–77°F)
S
Maximum Relative Humidity:
95%, noncondensing
C
 
A
 
U
 
T
 
I
 
O
 
N
If battery systems are located in the same room as the UPS, the battery manufacturer’s environmental
requirements should be followed if they are more stringent than the UPS requirements. Operating
temperatures above the recommended range will result in decreased battery life and performance, and may
reduce or void the battery warranty.
Table 3-3. Air Conditioning or Ventilation Requirements During Full Load Operation
Rating
Input/Output
Voltage
Heat Rejection
BTU/hr 
  1000 (kg−cal/hr)
Ventilation Required for
Cooling Air Exhaust
650 kVA
400/400
125 (31613)
Approximately 2265 liter/sec (4800 cfm)
With Field Installed UPM: 
Approximately 3020 liter/sec (6400 cfm)
480/480
127 (31933)
750 kVA
400/400
145 (36476)
480/480
146 (36845)
825 kVA
400/400
159 (40124)
480/480
161 (40530)