Toshiba 1700 Series Merkblatt

Seite von 2
 
UPS Connections
 
Standard Unit with 208/240V Input, 120/240V Output Transformer Module 
The figures below show the standard unit, consisting of one electronics module and one battery module, with the addition of 
the 208/240V input, 120/240V output transformer module.  The modules do not have to be stacked for the unit to operate; 
however, if the modules are to be stacked please refer to the 1700 Series user manual for instructions on interlocking 
modules. 
 
To connect the modules electrically follow these steps: 
 
 
Plug the gray power cord coming from the transformer 
module (labeled “Input from UPS”) into the gray 20A 
outlet on the back of the electronics module 
Plug the black power cord coming from the electronics 
module into the matching outlet on the back of the 
transformer module (labeled “Output to UPS”). 
Plug the blue battery connector coming from the 
battery module into the matching blue connector on 
the electronics module. 
Plug the black power cord coming from the 
transformer module (labeled “Input Power”) into the 
power source intended to supply power to the unit. 
Step 1 
Step 2 
Step 3 
Step 4