16    Periodic Maintenance/Parts Replacement
The G8000 is designed to provide long-term trouble-free power conditioning and backup.  Optimum 
performance can be best maintained by regular, periodic, preventive maintenance.
16.1    Scheduled Maintenance
The G8000 UPS should have scheduled maintenance performed on it annually by a factory-authorized 
service provider.  The preventive maintenance should include at minimum:
Clean UPS exterior
Clean UPS interior
Verify power supply voltages
Check for loose/overheated connections
Scan error log and correct potential UPS-related issues
16.2    Parts Replacement
The following list shows the recommended intervals for periodic replacement of certain UPS parts. 
Aluminum electrolytic capacitors: Replace once every 7-10 years.
Fuses: Replace once every 7-10 years
Cooling fan: Replace once every 7-10 years
Batteries (If applicable):  See the Backup Battery Cabinet manual for specific test, maintenance and 
replacement instructions.