3com PSE2500-A3 Benutzerhandbuch

Seite von 32
User Manual 
PSE2500-A3 External PoE
Power System 
Chapter 2  System Description
 
2-4 
rectifier failure, rectifier self-protection, the red LED is on. Once the 
alarm is gone, the red LED goes off. 
The controller of the PSE2500-A3 has two major functions: 
I. Monitoring the system operation status 
Inside PSE2500-A3 there is an AC sensor card, which can 
sample the AC input voltage. The sampled signal is sent into the 
controller for data processing. Once the input voltage is lower than the 
pre-set alarm level of the input low voltage, the controller reports an 
AC input under-voltage alarm. Likewise, if the input voltage is higher 
than the pre-set alarm level of the input high voltage, the controller 
reports an AC input over-voltage alarm. 
The sampled DC output voltage signal is also sent into the 
controller. Once the output voltage is lower than the pre-set alarm 
level of the output low voltage, the controller will reports a DC   Low 
alarm. Likewise, if the output voltage is higher than the pre-set alarm 
level of the output high voltage, the controller reports a DC output high 
alarm.  
The rectifier communicates with the controller through RS485 
bus. The working status of the rectifier is passed to the controller in 
this way. Once the rectifier has an alarm, the information is passed to 
the controller. The rectifier failure alarm includes: AC input failure, DC 
output failure, fan failure, output high, over temperature, and module 
shut-down. 
II. Communicate with deamon systems 
The controller supports China national standard protocol YD/T 
1104-2001. User can apply this protocol to read system information or