Power System 
Chapter 3  Safety
 
3-1 
Chapter 3  Safety 
3.1  Safety Statements 
Please read and follow all safety instructions and warnings before 
servicing the PSE2500-A3 system. Reference the individual module 
product manuals for additional safety statements specific to the 
modules. 
The device must be in a restricted access area (dedicated 
equipment rooms, equipment closets, or the like) where the 
applicable requirements of the device are met. 
The equipment must be in a controlled environment (an area 
where the humidity is maintained at levels that cannot cause 
condensation on the equipment, the contaminating dust is 
controlled, and the steady-state ambient temperature is 
within the range specified). 
Do not install this equipment at a combustible place. 
This equipment has been evaluated for use in a continuous 
ambient temperature of up to 50°C. 
Torque electrical connections conform to the values 
specified on labels or in the product documentation. 
Refer to the product documentation for the proper hardware. 
Use only the parts specified in the equipment documentation 
Improper fuses/circuit breakers may cause body injury or 
equipment damages. 
External circuit breakers must be sized as required by the 
applicable local codes. Refer to the equipment ratings to