APC SMX48RMBP2U Benutzerhandbuch

Seite von 21
7
Smart-UPS X  750/1000/1500 VA  120/230 Vac  Rack-Mount 2U
Configuration
UPS Settings
Start up settings
Configure these settings at initial start up, using the display interface or PowerChute
 software.
Note:
 During start up, use the display interface to configure these settings. If nothing is selected, the 
unit will use the default settings.
General Settings
Configure these settings at any time, using the display interface or PowerChute software.
Function
Factory Default Options
Description
Language
English
• English
• French*
• German*
• Spanish*
• Italian*
• Portuguese*
The language for the display interface.
*Language options will vary by model.
Local Power 
Quality
Good
• Good
• Fair
• Poor
Select the quality of input utility power.
• If Good is selected, the unit will go on battery power more often 
to provide the cleanest power supply to the connected 
equipment.
• If Poor is selected, the UPS will tolerate more fluctuations in 
power and will go on battery power less often. 
If unsure of the local power quality, select Good.
Menu Type
Standard
Standard or 
Advanced
The Standard menus display a limited set of menus and options. 
The Advanced menus include all parameters. 
Function Factory Default
Options
Description
High 
transfer 
point 
120 V: 140 Vac
120 V: 140-150 Vac
To avoid unnecessary battery usage, set the transfer point 
higher if the utility voltage is chronically high and the 
connected equipment is known to work under this 
condition. The 
POWER
 
QUALITY
 setting will automatically 
change this setting. 
Note: Use the Advanced Menus to configure this setting.
230 V: 280 Vac
230 V: 280-300 Vac
Low 
Transfer 
Point
120 V: 85 Vac
120 V: 75-85 Vac
Set the transfer point lower if the utility voltage is 
chronically low and the connected equipment can tolerate 
this condition.This setting may also be adjusted using the 
power quality setting.
Note: Use the Advanced Menus to configure this setting.
230 V: 170 Vac
230 V: 150-170 Vac
Nominal 
Output 
Voltage
230 V: 230 Vac
120 V: 120 Vac
230 V: 220, 230, 240 Vac
120 Vac: N/A
Set the nominal output voltage of the UPS on battery. This 
is available on 230 V models only.