CARETAKER PLUS INSTALLATION AND OPERATIONS MANUAL
 
 
21
 
 
Static Ram Read/Write Test 
The next test is for static ram. Since the Caretaker Plus has no static ram, this test is 
displayed as shown in TABLE 6 for consistency with other Rose products. 
 
Non-volatile Ram Tests 
The fourth and final power up test is for the non-volatile memory. A series of tests are 
performed. An error shown by the LEDs as error 4 indicates that the data in the 
nonvolatile memory has been corrupted. To attempt to rewrite the default parameters 
push SELECT switch then the ADVANCE switch. If the error condition goes out, the unit 
may be powered up again to see if it halts at error 4 again. If it still displays error 4, a 
fatal error has occurred and servicing is required. If the unit displays an error 45, the 
default parameters were not written correctly. This is a fatal error and servicing is 
required. 
If the unit recovers from the error the configuration parameters have been returned to 
their default settings and the unit must be configured again if these default settings are 
unacceptable. This condition should not normally occur. If it does it indicates that 
possibly the unit has been subjected to a strong static discharge or surge on its 
incoming power or signal lines. The other possibility is an internal chip failure. 
In addition to the data in the non-volatile ram, several others tests on the non-volatile 
ram are done. If any error 4 occurs and a reset to default does not correct it, the unit 
needs servicing. The additional errors listed below are for technical support purposes 
only. 
Front Panel Switches 
The front panel switches, labeled SELECT and ADVANCE, are used to enter and exit 
the configuration menu and to enter and exit the flow control display mode. These 
switches can be disabled under program control. This is done by either using the 
'Operator Switch Disable' command or through the configuration menu. Note that if 
these switches are disabled and the setting is stored in non-volatile memory, the only 
way to re-enable the switches is by resetting the Caretaker Plus to the factory default 
settings. See the 'Diagnostics' section for more information. 
Data LED, Busy LED, and Error LED 
The DATA LED flickers when data is sent in or out the shared device's port. When large 
blocks of data are sent to or received from the shared device, the DATA LED will be on 
continuously. The BUSY LED lights when the shared device is telling Caretaker Plus not 
to send data. For parallel models only, the ERROR LED lights to indicate a printer error 
or device off-line. 
Buffer Overflow Error Display (Serial Models Only) 
If any device fails to follow flow control protocol and transmits data when the Caretaker 
Plus is instructing it not to, an overflow may occur. If this happens, the ERROR LED and 
the overflowed port's LED will flash rapidly in unison. If the overflow was on the input 
buffer for the shared device, the BUSY LED will flash along with the ERROR LED. This 
indicates a buffer overflow has occurred and data may have been lost. This display will 
remain until acknowledged by pressing the advance switch. Other than lost data on the 
overflowed port, operation of the unit is not affected by this display. If the buffer is not 
cleared, data transfer continues, but the data may be unreliable. If more than one port 
overflows, multiple port LEDs will flash in unison with the ERROR LED. When this 
display occurs, the cabling may be incorrect, or a program that uses only X-on/X-off flow 
control may be accessing a port that is configured for DTR flow control.