Motor PTC Connections 
In order for the inverter to monitor the motor PTC (if fitted) it will be necessary to 
connect the Motor PTC to the Inverter Digital input 3 (DIN3) terminal. 
Connect the Motor PTC extension cable (provided with the Inverter) between the 
Inverter I/O terminals 3 & 4 and the Motor PTC terminals within the motor terminal 
housing. The arrangement is as shown in.Figure 2-12). 
NOTE 
DIN 3 must be configured to read the PTC input [(P0703 = 29) (external trip)] 
 
PTC Resistor connects between
terminals 4 (+24 V) and 3 (DIN 3).
 
Figure 2-12  PTC Connections