4  Using the MICROMASTER 411 / COMBIMASTER 411 
MICROMASTER 411 & COMBIMASTER 411    Operating Instructions 
 
6SE6400-5CA00-0BP0 
65
 
4.4 
Control Modes (P1300) 
The various modes of operation of the MICROMASTER 411 control the relation-
ship between the speed of the motor and the voltage supplied by the inverter. A 
summary of the control modes available are listed below: 
 
Linear V/f control 
P1300 = 0 
Can be used for variable and constant torque applications, such as conveyors 
and positive displacement pumps. 
 
Linear V/f control with FCC (Flux Current Control) 
P1300 = 1  
This control mode can be used to improve the efficiency and dynamic 
response of the motor. 
 
Quadratic V/f control 
P1300 = 2  
This mode can be used for variable torque loads, such as fans and pumps. 
 
Multi-point V/f control 
P1300 = 3  
Multi-point V/f allows the user to define their own V/f Characteristics. 
This characteristic uses two fixed coordinates and three pairs of variable 
coordinates. 
Fixed co-ordinates are:   Boost as defined in P1310 at 0 Hz. 
Nominal voltage P0304 at nominal frequency P0310 
Variable co-ordinates may be obtained from the following three pairs of 
coordinates 
P1320 (frequency) -P1321 (voltage) 
P1322 (frequency) -P1323 (voltage) 
P1324 (frequency) -P1325 (voltage) 
User programmable V/f characteristics are often used to provide correct torque 
at correct frequency, which can be useful when using the Inverter with 
synchronous motors. See Parameter List for further detail. 
 
4.5 
Faults and warnings 
LED Fault Indication  
Fault states and warnings are indicated by the LED within the control potentiometer 
on the inverter, see section 6.1 for further information. 
BOP fitted 
If a BOP is fitted, the fault states (P0947) and warnings (P2110) are displayed 
should a fault condition occur. For further details, please refer to section 6.2. 
AOP fitted 
If the AOP is fitted, fault and warning codes are displayed on the LCD panel.