6  Troubleshooting 
MICROMASTER 411 & COMBIMASTER 411    Operating Instructions 
 
6SE6400-5CA00-0BP0 
87
 
6.3.2 Alarm 
Messages 
Alarm messages are stored in parameter r2110 under their code number (e.g. 
A0503 = 503) and can be read out from there.  
A0501 Current 
Limit 
Possible Causes 
 
Motor power (P0307) does not correspond to the inverter power (P0206) 
 
Motor leads are too long 
 
Earth faults 
Diagnose & Remedy  
Check the following: 
 
Motor power (P0307) must correspond to inverter power (r0206) 
 
Cable length limits must not be exceeded 
 
Motor cable and motor must have no short-circuits or earth faults 
 
Motor parameters must match the motor in use 
 
Value of stator resistance (P0350) must be correct 
 
Motor must not be obstructed or overloaded 
 
Increase the ramp-up-time. 
 
Reduce the boost level (V/f control: P1311 & P1312, Vector control: P1610 & P1611) 
A0502 Overvoltage 
limit 
Possible Causes 
 
Overvoltage limit is reached 
 
This warning can occur during ramp down, if the dc-link controller is disabled (P1240 = 0) 
Diagnose & Remedy  
Check the following: 
 
Supply voltage (P0210) must lie within limits indicated on rating plate 
 
DC-link voltage controller must be enabled (P1240) and parameterized properly 
 
Ramp-down time (P1121) must match inertia of load 
 
Required braking power must lie within specified limits 
A0503 UnderVoltage 
Limit 
Possible Causes 
 
Main supply failed 
 
Main supply (P0210) and consequently DC-link voltage (r0026) below specified limit (P2172) 
Diagnose & Remedy  
 
Supply voltage (P0210) must lie within limits indicated on rating plate 
 
Supply must not be susceptible to temporary failures or voltage reductions 
 
Enable kinetic buffering (P1240 = 2) 
A0504 Inverter 
OverTemperature 
Possible Causes 
Warning level of inverter heat-sink temperature (P0614) is exceeded, resulting in pulse frequency 
reduction and/or output frequency reduction (depending on parameterization in P0610) 
Diagnose & Remedy  
Check the following: 
 
Load conditions and duty cycle must be appropriate 
 
Fan must turn when inverter is running 
 
Pulse frequency (P1800) must be set to default value 
 
Ambient temperature could be higher than specified for the inverter 
A0505 Inverter 
I
2
Possible Causes 
Warning level (P0294) exceeded, output frequency and/or pulse frequency will be reduced if 
parameterized (P0290) 
Diagnose & Remedy  
Check the following: