Siemens DataNET Hub (DNH) Benutzerhandbuch

Seite von 97
6  
••••  Introduction 
2000585-001 
DataNET Hub Specifications 
Dimensions 
Rack Mounted Package Configuration 
 
See Figure 1-5 for Outline Drawing and Dimensions 
 Wall-Mounted 
Package 
Configuration 
 
See Figure 1-6 for Outline Drawing and Dimensions 
 
Zone 1 - Wall-Mounted Package Configuration 
See Figure 1-7 for Outline Drawing and Dimension 
Housing, Explosion Protection, 
Ratings and Certifications 
Wall Mounted Configuration 
NEMA 3 (IP-54) 
CSA Certified for Class I, Division 2, Group A,B,C,D 
CENELEC non-Ex 
(Air purge is not required for fire protection as indicated; however, the 
unit may be air purged, if desired, for additional protection from envi-
ronmental elements.) 
Rack Mounted Configuration 
NEMA 2 (IP-20) 
CSA Certified for Class I, Division 2, Group A,B,C,D 
CENELEC non-Ex 
Zone 1 Configurations 
CENELEC approved EEx d IIC T6 Cortem CCA-04 enclosure 
Electromagnetic and Radio Frequency Compatibility and Electrical 
Safety 
CE Compliance; certified to 89/336/ECC (EMC directive) 
CE Compliance; certified to 73/23/EEC (Low Voltage directive) 
Tested per EN 61010-1 / IEC 1010-1 
Housing Materials and Colors 
Stainless steel (1.4016); Front and top are commercial gray B 
(RAL 7043), housing is light gray (RAL 7035) 
Weight 
Rack/Wall: 
15 kg (35 pounds) approximately 
Zone 1:   
33 kg (73 pounds)