Extreme networks 12802 Benutzerhandbuch

Seite von 160
Extreme Networks 1200 W DC PSU
 
BlackDiamond 12800 Series Switches Hardware Installation Guide
75
Minimum Software Required
You must be running ExtremeWare XOS version 11.3 or later for the system to recognize the DC PSU.
Pre-Installation Requirements
You need the following tools and equipment to install or remove a 1200 W DC PSU:
ESD-preventive wrist strap
Input DC power cable (provided with the DC PSU)
-48 V DC power source capable of providing 50 A dedicated power to each of the 1200 W DC PSUs 
installed in the switch
Thermal protective gloves (required for removal)
Installing the DC Wiring
The input DC cable for the DC PSU is supplied with the 1200 W DC PSU (see 
); you must use 
this cable with the DC PSU.
Figure 40: Input DC Power Cable for the 1200 W DC PSU
Each 1200 W DC PSU must be powered by a 50 A dedicated power source that delivers -40 to -72 VDC 
of constant power. Power distribution to the 1200 W DC PSU shall be provided using the -48 VDC 
harness provided. Power to the 1200 W DC PSU can be from either a 50 A UL-approved overcurrent 
protection breaker or an SELV- approved power source in accordance with IEC 60950-1 utilizing 50 A 
overcurrent protection.
The input DC cable has an input connector on one end and precut wire on the other end that goes to 
the DC power source. The connector end has a locking mechanism that locks onto the DC PSU to 
prevent accidental removal of the input DC cable.
If necessary, use appropriate termination lugs for 8 AWG (10 mm
2
) copper-stranded wire on cable ends 
of the cable to connect to the DC power source. 
The blue termination (-48 V) connects to a 50 A overcurrent protection circuit device, and the black 
(return) termination connects directly to the RTN bus of the DC power source. The green/yellow 
termination (ground) must connect to the same earth ground point as the switch.
EX_135
Return
Black: Return
Green/yellow:
Ground
Blue: -48V
Lock
Ground
10 ft.
-48Vdc