2.2.2  Cleanness Requirements 
Dust is a potential hazard to the safe operation of the switch. 
Falling on the equipment, it may cause electrostatic adsorption, and 
hence result in poor contact of the metal connectors or connection 
points. This is more likely to happen when the indoor relative humidity 
is low; in this case, it may not only shorten the device’s working life, 
but also incur communication failure. The requirements on dust 
content and particle diameter in the equipment room are shown in the 
following table: 
Table 2-1 
Requirements on dust content in the equipment room 
Physical active 
substance 
Unit 
Content 
Dust particle 
particle/m³ 
≤ 3 x 10
4
 (No visible dust 
on desk in three days) 
Note: Dust particle diameter ≥ 5µm 
 
Besides the requirements on dust, rigorous requirements are 
also set on the content of chloride, acid, and sulfide in the air of the 
equipment room. These kinds of harmful gas will accelerate metal 
corrosion and aging of certain parts. The equipment room should be 
protected from the intrusion of harmful gases such as SO
2
, H
2
S, NH
3
 
and Cl
2
. The limits of these kinds of harmful gas are shown in the 
following Table.