Maintenance
137
17.0 M
AINTENANCE
Minimal periodic maintenance of the STS2 is required. As with all electrical distribution components, 
the system should be regularly inspected for electrical connection integrity, signs of excessive temper-
atures, dirt accumulation, and proper system operation.
17.1 Proper Tightening of Nuts and Bolts
The recommended tightening torque for all nuts and bolts is as shown below, unless otherwise 
labeled. All power connections are designed to remain at proper torque throughout the lifetime of the 
unit. 
17.2 Testing the STS2
The STS2 includes comprehensive system alarms and fault detection to identify operational prob-
lems. To increase the degree of confidence of proper system operation, periodic transfer tests can be 
easily performed. For instructions for changing the preferred source and switching sources:
• For a Color Graphical Display unit, see 10.2 - Manual Transfer / Preferred Source 
17.3 Changing the Air Filter
A standard furnace filter is installed behind the air intake in the front door. The air intake allows air 
to circulate to cool the unit. Replace the filter when it becomes dirty and impedes air flow. The fre-
quency of changing or cleaning the filter depends on the location in which the unit is located.
The size of the filter is 1 in. x 25 in. x 25 in. (2.54 cm x 63.5 cm x 63.5 cm).
!
WARNING
Only qualified service personnel should perform maintenance on the static switch.
Lethal voltages exist inside the unit during normal operation. 
The unit is supplied by multiple ac power sources. disconnect and lock-out all power sources 
before working inside unit.
Table 25
Torque tightening
Bolt Shaft Size
Grade 5 -Imperial
Grade 8.8 -metric
Electrical Connections with 
Belleville Washers
in-lb
(pound-inch)
N-m
(Newton-meter)
in-lb
(pound.inch)
N-m
(Newton.meter)
10-32
25
3
35
4
1/4-20
53
6
80
9.0
5/16-18
107
12
180
20.4
3/8-16
192
22
240
27.1
1/2-13
428
48
480
54.3