Delta Electronics RTU-EN01 Benutzerhandbuch

Seite von 52
Modbus TCP Remote I/O Communication Module RTU-EN01 
DVP-PLC Operation Manual 
11
Code 
Indication 
How to correct 
F0 Returning 
to 
default setting 
-- 
F1 
RTU-EN01 being powered 
-- 
F2 
Power supply in low voltage 
Check if the power supply of the module works normally. 
F3 
Internal error. Manufacturing error.
1. Check if the settings of smart PLC are incorrect. 
2. Re-power RTU-EN01. If the error still exists, try step 3. 
3. Reset RTU-EN01. If the error still exists, send the module back to 
the manufacturer for repair.   
F5 
Network connection error 
Check if RTU-EN01 is connected normally to the network. 
F6 
Insufficient TCP connection 
Check if the number of connected modules exceeds the maximum. 
F7 
RS-485 setting error 
Check if the RS-485 communication format is correct. 
F8 
IP setting error 
1.  DHCP request failure. 
2.  IP setting error. 
3.  MASK setting error. 
4.  Gateway does not exist in the same subnet. 
5. Returning to default setting. 
F9 
Right-side module error 
Check if the configuration of the right-side module has been modified. If 
the error still exists, check if the number of I/O points exceeds the 
maximum and whether the there are more than 8 analog I/O modules 
connected. 
04 Slave 
error 
0b 
No response from station 
1. Check if RTU-EN01 and RS-485 is connected normally. 
2. Check if the series transmission speed is consistent with that of other 
nodes on the network. 
 
B R # 11 :   C o m m u n i c a t i o n   Ti m e - o u t   ( m s )
 
Explanations: 
For setting up the communication time-out. Default = 5,000ms. For example, if you wish to set up the 
communication time-out to 7 seconds manually, write 7000 to BR#11. Range: 5 ~ 65,535. 
 
B R # 1 2 :   C o m m u n i c a t i o n   D e l a y  Ti m e   ( m s )
 
Explanations: 
For setting up the minimum interval time between every Modbus command. Default = 0ms. For example, if you 
wish to set up the communication delay time to 100ms manually, write 100 into BR#12. Range: 0 ~ 65,535. 
 
B R # 1 3 :   T C P  C o n n e c t i o n   I d l e  Ti m e  ( s )
 
Explanations: 
For setting up the TCP connection idle time. Default = 30 seconds. For example, if you wish to set up the idle time 
to 7 seconds manually, write 7 into BR#13. Range: 5 ~ 65,535. 
 
B R # 2 3 :   N u m b e r   o f  A n a l o g   I / O   M o d u l e s
 
Explanations: 
Read the number of right-side modules from BR#23. Max. 8. 
 
B R # 2 4   ~   # 3 1 :   I D   o f   t h e   1
s t
  ~   8
t h
  A n a l o g   I / O   M o d u l e
 
Explanations: 
Read the ID of the 1
st
 ~ 8
th
 analog I/O modules from BR#24 ~ BR#31.