Modbus TCP Remote I/O Communication Module RTU-EN01 
 
DVP-PLC Operation Manual 
16 
5.3  Device Type & Device Address 
Discrete input 
Device type 
Modbus address (Hex) 
6-digit Modbus address (Dec) 
Number 
RX 
0x0400 ~ 0x04FF 
101025 ~ 101280 
256 
Coil 
RY 
0x0500 ~ 0x05FF 
001281 ~ 001537 
256 
0x1600 ~ 0x160F 
005633 ~ 005649 
16 
0x1900 ~ 0x190F 
006401 ~ 006416 
16 
0x1E00 ~ 0x1E0F 
007681 ~ 007696 
16 
Holding register 
Device type 
Modbus address (Hex) 
6-digit Modbus address (Dec) 
Number 
BR 0x0000~0x0040 
400001~400064 
64 
T 0x1600~0x160F 
405633~405649 
16 
C 0x1E00~0x1E0F 
407681~407696 
16 
RCR 0x3000~0x3190 
412289~412689 
400 
Setting up Software 
This section gives instructions on how to set up RTU-EN01 by DCISoft and explanations on each setup page. 
RTU-EN01 is set up by UDP port 20006; therefore, you have to be aware of the relevant settings of the firewall. 
See the explanations below on the software.
 
6.1  Setting up Communications & Searching for Communication Modules in DCISoft 
„
 Broadcast 
search 
1.  Open DCISoft on the PC and click on the “IP Search” icon.