Sun Fire X4100/X4100 M2 and X4200/X4200 M2 Servers Installation Guide • May 2007
Powering On and Off the Server
You have to apply only standby power to the server at this point so that you can 
perform initial configuration o f the service processor. Procedures for powering on to 
main power mode and for shutting down from main power mode are also included 
in this section. 
Applying Standby Power for Initial Service 
Processor Configuration 
Use this procedure to apply standby power to the service processor (SP) before 
initial configuration.
Caution – 
Do not operate the server without all fans, component heatsinks, air 
baffles, and the cover installed. Severe damage to server components can occur if 
operated without adequate cooling mechanisms.
1. Connect grounded AC power cords to the AC power connectors on the back panel 
of the server and to grounded AC power outlets.
In standby power mode, the Power/OK LED on the front panel flashes, indicating 
that the SP is working. See 
 for the LED location.
Note – 
At this point, standby power is supplied only to the Graphics Redirect and 
Service Processor (GRASP) board and power supply fans. You can proceed to 
 to begin initial configuration. Do not apply main power to the rest of the 
server until you are ready to install a platform operating system. 
2. Continue with initial software setup tasks, as described in