FieldServer FS-8700-31 Benutzerhandbuch

Seite von 26
FS-8700-31 
Siemens 
TIWAY 
           Page 
13 
of 
23 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA  Web:www.fieldserver.com 
Tel: (408) 262-2299   Fax: (408) 262-9042   Toll_Free: 888-509-1970   email: support@fieldserver.com
 
 
The above map descriptor will continuously execute the indicated host adapter command and will store the 
following parameter values in the data array “HIU_Config”: 
Offset Parameter 
Dipswitch 1 and 2 settings 
Config flag ( 0 = HIU not configured, 1 = HIU configured ) 
Option 01 configuration value 
Option 02 configuration value 
Option 03 configuration value 
 
 
4.4.6.3. 
Report Adapter Configuration 
Reports the Adapter Configuration option values that was used to configure the adapter. 
 
Map_Descriptor_Name, Data_Array_Name, 
Data_Array_Offset, Function, Node_name, TIWAY_Host_Adapter_Cmd, Length, 
C39_REP_ADAP_CONFIG, Adapter_Config, 
0, 
RDBC, PLC_01,  Report_Adapter_Config,  6, 
 
Scan_Interval 
0s 
 
The above map descriptor will continuously execute the indicated host adapter command and will store the 
following parameter values in the data array “Adapter_Config”: 
 
Offset Parameter 
Dipswitch 1 and 2 settings 
Config flag ( 0 = Adapter not configured, 1 = Adapter configured ) 
Option 01 configuration value 
Option 02 configuration value 
Option 03 configuration value 
Option 04 configuration value 
 
4.4.6.4. 
Report Network Manager Configuration 
Reports the Network Manager option values that was used to configure the network manager. 
 
Map_Descriptor_Name, Data_Array_Name, 
Data_Array_Offset, Function, Node_name, TIWAY_Host_Adapter_Cmd, Length,