7.4. 
Step 4: Write Ladder Program to Send Output Data to Data Arrays 
This step demonstrates how to write data to the Data Array Out[0] 
 
•  Create a Controller Tag called Lon_Out_01 of type REAL[80].  
•  Add a new rung to the Ladder program and add a MOV element to move a block number 
value of 1 into Lon_Out_01[2].  
•  Finally add a CPS (Synchronous Copy File) element to copy the full Lon_Out_01 tag into 
the Output Image Tag. 
 
 
 
The LonWorks Data are present from Lon_Out_01[4] to Lon_Out_01[79] 
 
You  can  create  a  User Defined  Data Type  to replace  the type  of  Lon_Out_01 mapping  the 
points to LonWorks point names.  
 
Very Important Note! 
It  is  very  important  to  only  update  all  the  data  of  the  Output  Image  Tag  once  using  a 
Synchronous  File  Copy  element.    It  is  not  permissible  to  update  the  block  number  into  the 
Output Image Tag and then the data as this will cause an asynchronous transfer of data. 
 
7.5. 
Step 5: Download the RSLogix Program and Run 
Use the Who Active or Communications Path directly to Download and Run the Program on 
the Controller / CPU. 
 
7.6. 
Step 6: Set up the third party connection 
In this example, this step would involve binding the LonWorks variables using a LonWorks 
Network Manager..