Appendix A.4.  Dealing with ControlLogix RPI Settings 
When  setting  up  the  SlotServer  for  ControlLogix,  it  is  necessary  to  select  the  Request 
Packet  Interval  (RPI).    The  RPI  is  the  rate  at  which  data  is  transferred  to  and  from  the 
SlotServer  IO  buffers.    The  following  factors  need  to  be  considered  when  deciding  on  an 
RPI: 
1.  Minimum RPI setting for the SlotServer is 100ms. 
2.  The Scan_Interval parameter of the two Logix Map descriptors must be larger than the 
RPI to ensure smooth communications and prevent timeouts. 
3.  The number of message blocks used does not affect the RPI setting, but will affect the 
effective  update  rate  for  any  one  message  block.    The  effective  update  rate  for  data 
to/from  the  SlotServer’s  Data  Arrays  to  the  Logix  CPU  tags  is  the  scan  interval  of  the 
block since data is updated to the block every scan interval.  Increasing the number of 
blocks  will  decrease  the  effective  update  rate  per  block.    This  update  rate  does  not 
include  the  time  taken  to  obtain  data  from  the  third  party  network,  which  is  dependant 
entirely on the third party protocol involved. 
4.  The program scan rate should be set to run faster than the RPI.  We recommend twice 
as fast.  If the ladder program scan is slower than the RPI rate, it would be possible to 
miss  some  blocks  altogether.    It  is  further  recommended  that  diagnostics  be  added  to 
the ladder program to detect missed blocks 
 
The effective update rate can be calculated using the following formula: 
 
Effective update rate (EUR) = Scan interval * (number of msg block pairs
6
 
e.g.  (EUR)  
=  
0.2s * 1 = 0.2s 
when using only one input and output block 
 
e.g. (EUR)  
=  
0.2s * 25 = 5s                 
when using the full LonWorks Open Interface configuration. 
 
                                                 
6
 a message block pair consists of an output and input block