CONNECTION TO THE DEVICE 
The 12VDC power supply received with the unit needs to be plugged into a power source and then connected to 
the  back  of  the  FieldServer.    Ensure  that  the  power  supply  used  complies  with  the  specifications  provided  in 
Section 2.2. 
 
Figure 3-1: View of back of FS-B-OPC-01 showing Connection Ports 
3.1 
RS-232 connection 
The FS-B-OPC-01 Series FieldServer is shipped with the RS-232 port activated.  
Connect the FS-8917-10 cable (supplied) between the RS-232 port on the OPC FieldServer and the device as shown 
in the connection diagram.  Note that the cable labels refer to the Tx and Rx signals on the FS-B-OPC and must be 
connected to the opposite signal on the remote device.  
FS-8917-10
FS-8917-10
Tx
Rx
Tx
GND
Labels refer to 
signal reference 
on FS-B-OPC
Remote RS-232 Device
GND
Rx
DB9M on FS-B-OPC
 
Figure 3-2: FS-B-OPC Serial RS-232 Connection 
3.1.1  Connector Pinouts 
Wire Color 
FS-OPC 
Remote Device 
Signal  Pin #  Signal 
Pin # 
Green 
Tx 
Rx 
Red 
Rx 
Tx 
Black 
GND 
GND 
 
 
 
 
 
 
 
Power 
Serial 
Ethernet