FieldServer FS-B-OPC-01 Benutzerhandbuch
FS-B-OPC-01 Series FieldServer Start-up Guide
Page 6 of 10
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: 888-509-1970 email: support@fieldserver.com
3
CONNECTION TO THE DEVICE
The 12VDC power supply received with the unit needs to be plugged into a power source and then connected to
the back of the FieldServer. Ensure that the power supply used complies with the specifications provided in
Section 2.2.
the back of the FieldServer. Ensure that the power supply used complies with the specifications provided in
Section 2.2.
Figure 3-1: View of back of FS-B-OPC-01 showing Connection Ports
3.1
RS-232 connection
The FS-B-OPC-01 Series FieldServer is shipped with the RS-232 port activated.
Connect the FS-8917-10 cable (supplied) between the RS-232 port on the OPC FieldServer and the device as shown
in the connection diagram. Note that the cable labels refer to the Tx and Rx signals on the FS-B-OPC and must be
connected to the opposite signal on the remote device.
in the connection diagram. Note that the cable labels refer to the Tx and Rx signals on the FS-B-OPC and must be
connected to the opposite signal on the remote device.
FS-8917-10
FS-8917-10
Tx
Rx
Tx
GND
Labels refer to
signal reference
on FS-B-OPC
Remote RS-232 Device
GND
Rx
DB9M on FS-B-OPC
Figure 3-2: FS-B-OPC Serial RS-232 Connection
3.1.1 Connector Pinouts
Wire Color
FS-OPC
Remote Device
Signal Pin # Signal
Pin #
Green
Tx
3
Rx
8
Red
Rx
2
Tx
1
Black
GND
5
GND
4