FieldServer FS-X20 Benutzerhandbuch

Seite von 13
 
 
 
 
 
 
 
 
 
 
 
Start-up guide 
Page 11 
FS-X20 Series FieldServer Start-up Guide (07-2005) 
Appendix B. 
LED Functions 
Rx
Tx
Rx
Tx
Ethernet
EIA232
USB
EIA485
Power OK
FieldBus Active
-
+
Serial
FieldServer Running
Hot Standby Active
Node Offline
Configuration Error
Comm Error
System Error
IP Request
 
 
Light 
Description  
Ethernet  Link 
OK. 
This  light  relates  to  the  Ethernet  network  port  provided  on  the  FieldServer.    The 
Ethernet  Link  OK  light  shows  steady  green  when  the  physical  connection  to  the 
network hub is healthy.  The Rx (Receive) light flashes green when the FieldServer 
is receiving data from the network.  The frequency of flashing is directly related to the 
network  activity.    It  does  not  necessarily  mean  data  is  being  received  by  the 
FieldServer.  The Tx (Transmit) light flashes yellow when the FieldServer is sending 
data.    The  frequency  of  flashing  is  directly  proportional  to  the  frequency  of  data 
transmission. 
Power OK 
This  is  the  power  light  and  should  show  steady  green  at  all  times  when  the 
FieldServer is powered. 
Fieldbus 
Active 
This light should show steady green when the Fieldbus connection is active. 
FieldServer 
Running 
The  light  should  flash  green  once  per  second  once  the  FieldServer  has  booted  up.  
Note  that  it  may  take  a  while  from  power  up  to  booting  up  the  FieldServer  if  the 
loaded  configuration  is  particularly  large.    The  light  indicates  that  the  FieldServer 
firmware is running. 
Configuration 
Error 
A  steady  amber  light  will  indicate  a  configuration  error  exists  in  the  active 
configuration.  See the Error Screen in the Remote User Interface for a description of 
the configuration error. 
Comm Error 
A  steady  red  light  will  indicate  the  communications  problem  if  there  is  a  configured 
node connected to the FieldServer that is offline.  To establish the cause of the error, 
go to the error screen of the RUI interface. 
Hot 
Standby 
Active 
Not applicable 
Node Offline 
An  amber light  will flash  when a configured node on  the FieldServer is  detected as 
being offline.  The flash will repeat after every unsuccessful retry. 
System Error 
A  steady  red  light  will  indicate  there  is  a  system  error  on  the  FieldServer.    If  this 
occurs, immediately report the related “system error” shown in the error screen of the 
RUI interface to FieldServer Technologies for evaluation. 
EIA-232 
These lights, built  into the connector, are related to the RS-232 serial port provided 
on  the  FieldServer.    The  Rx  (Receive)  light  flashes  green  when  the  FieldServer  is 
receiving  data  and  the  Tx  (Transmit)  light  flashes  yellow  when  the  FieldServer  is 
sending  data.    The  frequency  of  flashing  is  directly  proportional  to  the  frequency  of 
data transfer.