Liebert STS2 Touch Screen Display
90
Figure 53 User settings dialog box
Source Set Points
The Source 1/2 Set Points allows you to configure trigger points for each input source (1 or 2) for the 
Liebert STS2 via a keypad dialog or HI/LO dialog box. The source numbers do not designate the 
source as the preferred or alternate source. The numbers simply identify the input source. See 10.2 - 
Manual Transfer / Preferred Source Selection to set the preferred source.
The Set Points are based on values in relation to the nominal voltage required for the Liebert STS2. 
UV refers to under voltage, meaning the amount of voltage below the nominal voltage. OV refers to 
over voltage, or the amount of voltage over the nominal voltage.
• Fast UV Setting (%) — if the voltage drops below this set percentage of the nominal voltage, the 
Liebert STS2 transfers from the current source to the opposite source.
• Slow UV Setting (%) — if the voltage remains this set percentage below the nominal voltage for 
the period of the slow detection delay, the Liebert STS2 transfers from the current source to the 
opposite source.
• Slow UV detection delay — the number of cycles that the source must remain below the Slow UV 
Setting before the Liebert STS2 transfers.
• OV Setting (%) — if the voltage exceeds this set percentage of the nominal voltage for the period of 
the OV detection delay, the Liebert STS2 transfers from the current source to the opposite source.
• OV Detection Delay — the number of cycles that the source must remain above the OV Setting 
before the Liebert STS2 transfers sources.
• I-PK Xfer Lockout — if current from the source exceeds this threshold, the Liebert STS2 disables 
source transfers, and has to be reset either manually or automatically. The type of reset is 
configured under the User Settings.