Prior to mounting the SPD, verify that the device has the same voltage 
rating as the power distribution system in which it is installed by comparing 
the nameplate voltage or model number on the SPD with the nameplate of 
the electrical distribution equipment.
The specifier or user of the device should be familiar with the configuration 
and arrangement of the power distribution system in which any SPD is to 
be installed. The system configuration of any power distribution system is 
based strictly on how the secondary windings of the transformer supplying 
the service entrance main or load are configured. This includes whether 
or not the transformer windings are referenced to earth via a grounding 
conductor. The system configuration is not based on how any specific load 
or equipment is connected to a particular power distribution system. See 
Table 1 for the service voltage of each SPD. 
 
Table 1: APC Modular Panel SPD Voltage Ratings/Model Number
ELECTRICAL 
Voltage Rating 
Service voltage
configuration
120/208 wye
3Ph. Wye 4-wire +G
3Ph. Wye 4-wire +G 
3Ph. Wye 4-wire +G
220/380 wye
PMF3S-A
PMF3DS-A
PMP3S-A
PMP3DS-A
PMG3S-A
PMG3DS-A
PML3S-A
PML3DS-A
120kA
120kA
120kA
120kA
120kA
120kA
120kA
120kA
PMF4S-A
PMF4DS-A
PMP4S-A
PMP4DS-A
PMG4S-A
PMG4DS-A
PML4S-A
PML4DS-A
120/208 wye
120/240 wye (Single Phase)
120/240 wye (Single Phase)
1Ph. Wye 3-wire +G
1Ph. Wye 3-wire +G
277/480 wye
277/480 wye
347/600 wye
347/600 wye
3Ph. Wye 4-wire +G
3Ph. Wye 4-wire +G
3Ph. Wye 4-wire +G
PMH4DSLM-A
120/208 wye
120/208 wye
120/240 wye (Single Phase)
120/240 wye (Single Phase)
277/480 wye
277/480 wye
347/600 wye
347/600 wye
3Ph. Wye 4-wire +G
3Ph. Wye 4-wire +G
3Ph. Wye 4-wire +G
1Ph. Wye 3-wire +G
1Ph. Wye 3-wire +G
3Ph. Wye 4-wire +G
3Ph. Wye 4-wire +G
3Ph. Wye 4-wire +G
3Ph. Wye 4-wire +G
160kA
160kA
160kA
160kA
160kA
160kA
160kA
160kA
160kA
MoDel nuMBer
ka rating
Terminals are provided for phase (line), neutral, and equipment ground 
connections. The SPD terminals accept a range of #12 to #2 AWG (34 
mm
2
) copper wire for phase, neutral, and ground connectors. Torque 
connections to the following values.
Table 2: Installation Torque
Power Connection
Terminal Torque
W/O Disconnect
W/ Disconnect
AØ, BØ, CØ & N
35 lb-in (4N·M)
50 lb-in (5.7N·M)
Ground
50 lb-in (5.7N·M)
The use of fusible disconnects requires a fuse with a melting characteristic 
greater than the per phase (Clearing) I
2
t of the SPD to prevent nuisance 
operation of the disconnect fuses during a surge. (Refer to caution 
statement “LOSS OF BRANCH CIRCUIT POWER AND SURGE 
PROTECTION” on page 2 for further information) 
Terminals, Wire Size and 
Installation Torque
Disconnect Means (External)
ELECTRICAL
APC MODULAR PANEL PRODUCTS Surge Protective Device (SPD)
8
PML-4Y-DC-DL-A
347/600 wye
3Ph. Wye 4-wire +G
160kA
*
*
Redundant 160kA system