SPeCIfICaTIonS & DIMenSIonS
Table 1 – Specifications 
Voltage
kw
Maximum 
steam capacity
nominal Current draw  
(amps)
Humidifier unit 
operating weight
gal/day
amps
lbs
120V
1 .4
11 .5
11 .5
23
208V
2 .4
20 .5
11 .5
23
240V
2 .8
23 .3
11 .5
23
The Aprilaire
®
 Model 800 Canister Steam Humidifier delivers 
humidity in the form of steam to the conditioned space via 
the HVAC system duct or optional Aprilaire Model 850 Fan 
Pack . The humidifier generates steam by energizing two 
electrodes that extend into a canister of water . Current 
flowing between the electrodes causes the water to boil, 
creating steam . Water is introduced to the humidifier through 
a fill valve to a fill cup located in the top of the cabinet . The 
fill cup serves as an overflow reservoir and provides an air 
gap between the humidifier and water source . The steam 
canister is filled from the bottom . The canister is seated 
in a drain cup assembly which includes a drain valve . The 
drain and fill valves work together to maintain water level 
in the canister to deliver the rated steam capacity based 
on the electrical conductivity of the water and to temper 
drain water . See 
figure 1 for representation of fill and drain 
system and canister . 
Steam is delivered into the airstream through a dispersion 
tube mounted in the HVAC system ductwork . Openings in the 
dispersion tube are fitted with “tubelets” which extend into 
the center of the tube . The design of the dispersion tube and 
tubelets distribute steam over a wide area in the duct and 
direct any condensed moisture back into the steam hose .
PRInCIPleS of oPeRaTIon
fIGURe 1 – fill and Drain System and Canister
90-1522
 
Steam
Outlet
Drain
Supply
Water
Drain Cup
Drain Valve
Canister
Electrodes
High Water
Level Sensor
Flow Control
Orifice
Inlet
Fill Valve
Overflow
Fill
Fill Cup
3