APC Symmetra LX 8kVA UPS SYA8K16PXR Benutzerhandbuch

Produktcode
SYA8K16PXR
Seite von 25
C
HAPTER 
4:
  
T
ROUBLESHOOTING
 
 17  
Condition 
PowerView Message 
Reason 
Corrective Action 
Redundancy Restored.  
Power module redundancy loss 
occurred and was restored. 
Additional modules have been 
installed or the load has been 
reduced. 
Load is No Longer above 
Alarm Threshold.  
The load exceeded the load alarm 
threshold. The situation has been 
corrected by a load decrease or 
threshold increase. 
General 
Status 
(continued) 
Min Runtime restored. 
The system runtime dropped 
below the configured minimum 
runtime and was restored.  
Additional battery modules were 
installed, the existing battery 
modules were recharged, the load 
was reduced, or the threshold was 
raised. 
No corrective action 
necessary. 
Bad Battery Module.  
A battery module has failed and 
requires replacement. 
Bad Power Module.  
A power module has failed and 
requires replacement. 
Intelligence Module is 
installed and failed.  
The intelligence module in the 
lower IM slot has failed. 
Module 
Failure 
Redundant Intelligence 
Module is installed and 
failed. 
The intelligence module in the 
upper IM slot has failed. 
Refer to module installation in 
the Symmetra LX Physical 
Installation Guide.
 
Load is above kVA alarm 
threshold.  
The load has exceeded the user-
specified load alarm threshold.  
Option 1: Reduce the load. 
Option 2: Use the PowerView 
interface to raise the alarm 
threshold. 
Threshold 
Alarm 
Redundancy has been 
lost. 
The UPS no longer detects 
redundant power modules. The 
power module(s) failed or the load 
increased. 
Option 1: If possible, install 
additional power modules. 
Option 2: Decrease the load. 
Option 3: Disable the 
redundancy alarm by setting 
redundancy to zero. 
(Startup>Setup>Alarms> 
Redundancy>Zero)