Cooper Lighting UEL Series Merkblatt

Seite von 1
658
INDUSTRIAL & HAZARDOUS LOCA
TION 
Emergency Lights
COOPER LIGHTING
COOPER LIGHTING - SURE-LITES
®
D I M E N S I O N S
• NEMA 4X, UL50 Listed
• Dual-voltage input
120/277VAC, 60Hz, Isolation
Transformer
• Die cast aluminum housing 
• Powder coat finish
• UV stable, glass-clear
polycarbonate, vandal
resistant shield (.150” thick)
with Torx head tamperproof
screws, stainless steel
• (2) Adjustable 12W, MR16
lamps
• Nickel Cadmium Battery
• Fully recharged in 24 hours
• Vandal Proof
• Watchguard EMS 
Self-Diagnostic System
• Photocell Test Switch
(requires accessory LASER
for activation)
• Push-in AC power
connectors facilitate
installation
• UL 924 Listed 
Self-Diagnostics, UL 924
Outdoor Wet Location
Listed (suitable for wet and
damp locations)
• T1 Haz Lamp Rating
• NSF, National Sanitation
Foundation/Splash Zone
(for Food Processing)
• IP66, Ingress Protection
from IEC (International
Electrical Commission)
• Cleanroom Class 10,000
• Patent Pending
UEL SERIES
U LT I M AT E   E M E R G E N C Y
L I G H T
E M E R G E N C Y   L I G H T I N G
D E S C R I P T I O N
The Sure-Lites UEL NEMA 4X
Emergency Light is designed for
those emergency lighting
applications where ruggedness and
dependability are a must. The UEL’s
housing is constructed of durable
die cast aluminum combined with
the strength of a clear
polycarbonate shield. Designed for
the most severe environments, the
UEL Emergency Light will provide
maximum performance against
rain, moisture, cold, corrosives and
dust. The UEL’s standard features
include nickel cadmium battery,
self-diagnostics, photocell LASER
test and MR16 lamps that provide
the customer with a long life, low
maintenance, dependable, severe
environment approved emergency
lighting unit in those conditions
when reliability is crucial. The
injection molded, polycarbonate
shield provides protection against
moisture, rain, and vandalism, as
well. (4) Torx head tamperproof
screws with center-pin reject
provide additional vandal-proof
security. Two adjustable 12W MR16
lamps provide maximum path of
egress coverage providing a bright,
even illumination during power
outages. The unique design and
features make the UEL Emergency
Light compatible in food
processing facilities, outdoor
parking garages, walk-in freezers
and other indoor/ outdoor severe
environments. The UEL Emergency
Light is UL listed for –35°C (-31°F)
to +50°C (+122°F) ambient
environments.
S e l f - D i a g n o s t i c s
The self-diagnostic unit will automatically perform all
tests required by UL924 and NFPA 101. The system
indicates the status of the unit at all times using the
LED indicator near the test switch on the side of the
unit. A 90 minute battery power (emergency mode)
simulation test will occur randomly once every six
months.
A 30 second battery power simulation test will occur
every 30 days.
O R D E R I N G   I N F O R M AT I O N
S A M P L E   N U M B E R :   U E L 1 S D
Family
UEL1
=Nema 4X 
Emergency
Light
Housing
Finishes
Blank
=Silver
BK=Black
WH=White
Accessories (order separately)
LASER=Key Chain, Red Laser Pointer
(activation tested at 30 feet)
UXPKA=Pendant Kit Adapter (fitting adapts
to 1/2" NPT threaded pendant)
VRSD=#8 Centerpin Torx Screwdriver
SD=Self Diagnostics
(Standard)
E L E C T R I C A L   R AT I N G S
Model
DC Voltage
1 1/2 Hours
UEL1SD
12
24
Rated Wattage
to 87 1/2% of Rated D.C. Voltage
Lamp Information
Type
Wattage
Number
Spacing
1
MR16
12
29-141
50.0'
Options
A=Ammeter
V=Voltmeter
TDM=Time Delay Monitor
HAZ=Hazardous
Locations (Class I,
Division 2, Groups
A, B, C, D)
(1)
The "Rule of Thumb" spacing guidelines are designed to achieve 1 foot-candle average and 0.1 foot-candle minimum with a 40:1
maximum/minimum ratio. The corridor used is 100 feet long, 9 feet ceiling with a 6 feet wide walkway and 3 feet path of egress.
The reflectances are 80% ceiling, 50% walls and 20% floors. The fixture mounting height is 7.0 feet with a lamp head angle of 45 degrees.
Cooper Lighting assumes no responsibility for local requirements or specific project variables. This is a guideline to be used as a design aid,
not as guarantee of any code compliance.
-31°F to +122°F
SPLASH ZONE
Laser Test
6 3/16”
[157mm]
15 1/4”
[389mm]
6 11/16”
[169mm]
E n e r g y   D a t a
Input Current (Max.): 
Model No.
120V  
277V 
UEL1SD
.09A
.03A