FBP Series Fluorescent Emergency Ballast
FBP50
Page 1 of 1
One or Two Lamp Operation 1,400 Lumens
Lightolier is a Philips group brand
The FBP Series quickly converts standard fluorescent luminaires into emergency luminaires.
13.3”
(33.9 cm)
2.4”
(6.1 cm)
1.5”
(3.8 cm)
Complete Fixture consists of ballast unit. Select options and accessories below.
Model #
Max. Lumens
Lamp Operation
FBP50
1,400
One or Two
Lamp Operation and Performance (continued)
Non-Emer. Emer. Op.
Max.
Max.
Emer.
Lamp
Base
Lumen
Lumen
Lamp
Type
Watt.
Type
Output
Output
Operation
F96T12HO
95
R17D/Recessed
8000
1100 - 1400
One
F48T12
110
R17D/Recessed
6200
1100 - 1400
One
F17T8
17
G13/Med Bi-Pin
1325
1100 - 1400
One or Two
F25T8
25
G13/Med Bi-Pin
2080
1100 - 1400
One or Two
F32T8
32
G13/Med Bi-Pin
2850
1100 - 1400
One or Two
F32T8/U
32
G13/Med Bi-Pin
2700
1100 - 1400
One or Two
F40T8
40
G13/Med Bi-Pin
3600
1100 - 1400
One
F96T8
59
FA8/Single-Pin
5800
1100 - 1400
One
F27BX
27
2G11/4--Pin
1800
1000
Two
F282D
28
GR10Q-4/4 Pin
2050
1100
One or Two
F382D
38
GR10Q-4/4 Pin
2850
1000
One or Two
F39/36BX
39
2G11/4--Pin
2850
1100
One or Two
F40/30BX
40
2G11/4--Pin
3150
1100
One
F50BX/FT55
50-55
2G11/4--Pin
4300-4800
1100
One or Two
F96T12HO
95
R17D/Recessed
8000
1100 - 1400
One
F96T12VHO
95
R17D/Recessed
8000
1100 - 1400
One
Notes:
1. Maximum non-emergency lumen output can vary based on lamp manufacturer, ambient
operating temperature, and ballast manufacturer.
2. Maximum emergency lumen output is based on total output of one or two lamps, and can
vary based on lamp manufacturer and ambient operating temperature.
3. Maximum emergency lumen output is supported for a full 90 minutes of operation.
4. Consult factory for compatibility, operation and performance of lamp types not listed.
4. Consult factory for compatibility, operation and performance of lamp types not listed.
Features
1. Lamp Operation: Operates the following lamp types: T8 linear fluorescent,
T12 linear fluorescent, T9 circline, T12 U-bent, T5 long compact fluorescent,
compact 4-pin fluorescent. See Lamp Operation and Performance table for
specific lamp performance and operation
compact 4-pin fluorescent. See Lamp Operation and Performance table for
specific lamp performance and operation
.
2. Illumination: Provides 90 minutes of emergency illumination, and produces
a maximum of 1,100 to 1,400 lumens initial emergency light output. Can be
used with most 17w to 215w (2’ - 8’) T8, T10 or T12 fluorescent lamps with-
out integral starters including U-shaped, HO, VHO, circline, energy saving,
and 4 pin compacts. It is also compatible with most 1, 2, 3 and 4-lamp elec-
tronic, standard, energy saving and dimming AC ballasts.
used with most 17w to 215w (2’ - 8’) T8, T10 or T12 fluorescent lamps with-
out integral starters including U-shaped, HO, VHO, circline, energy saving,
and 4 pin compacts. It is also compatible with most 1, 2, 3 and 4-lamp elec-
tronic, standard, energy saving and dimming AC ballasts.
3. Housing: Constructed of 20 gauge steel with a high temperature powder
coat paint finish. Slim housing allows for wireway channel mounting on most
recessed luminaires.
recessed luminaires.
4. Electronics: 120/277 VAC dual voltage input with surge-protected, solid-
state circuitry. Charging system is complete with AC indicator lamp and test
switch.
switch.
5. Battery: Maintenance free, sealed nickel cadmium battery has an estimated
service life of 10 years, and an operating temperature range of 32°F (0°C) to
131°F (55°C).
131°F (55°C).
6. Input Power Requirements: 4 watts max.
7. Warranty: Electronics: 5 years; Battery: 5 years.
7. Warranty: Electronics: 5 years; Battery: 5 years.
Code Compliance
UL 924 listed, damp location listing optional.
UL listed for use within sealed and/or gasketed luminaires.
UL listed for use within sealed and/or gasketed luminaires.
Options
EX = Special Input Transformer for 220 VAC/50 Hz, 240 VAC/50Hz.
Contact factory for other input voltages and frequencies.
DL = UL Damp Location Listing
Contact factory for other input voltages and frequencies.
DL = UL Damp Location Listing
Accessories
CCAPS = Wire bundle cover for mounting external to luminaire.
RTS = Single gang aluminum faceplate pre-drilled to accommodate remote
installation of test switch and pilot light.
RTS = Single gang aluminum faceplate pre-drilled to accommodate remote
installation of test switch and pilot light.
Lamp Operation and Performance
Non-Emer. Emer. Op.
Max.
Max.
Emer.
Lamp
Base
Lumen
Lumen
Lamp
Type
Watt.
Type
Output
Output
Operation
F20T12
20
G13/Med Bi-Pin
1275
1100 - 1400
One or Two
F30T12
30
G13/Med Bi-Pin
2350
1100 - 1400
One or Two
F40T12
40
G13/Med Bi-Pin
2650
1100 - 1400
One or Two
F40T12/U
40
G13/Med Bi-Pin
3100
1100 - 1400
One or Two
F48T12
40
FA8/Single-Pin
2875
1100 - 1400
One or Two
F60T12
50
FA8/Single-Pin
3600
1100 - 1400
One
F72T12
55
FA8/Single-Pin
4500
1100 - 1400
One
F96T12
75
FA8/Single-Pin
5500
1100 - 1400
One
F24T12HO
35
R17D/Recessed
1620
1100 - 1400
One
F36T12HO
45
R17D/Recessed
2800
1100 - 1400
One
F48T12HO
60
R17D/Recessed
5150
1100 - 1400
One
F60T12HO
75
R17D/Recessed
4050
1100 - 1400
One
F72T12HO
85
R17D/Recessed
6350
1100 - 1400
One
Nickel Cadmium Battery