BEA LO-21P Benutzerhandbuch

Seite von 13
75.5079.08 20061129 
 
Page 2 of 13 
 
ELECTRICAL 
INSTALLATION – 
OPTION 1 – 
STANDARD 
WIRING 
 
STANDARD WIRING 
 
 
 
WIRE CONNECTIONS 
Black Motor 
Input 
- 
Red 
Motor Input + 
Purple 
Bodyguard COM. Pin 3 
White 
Bodyguard Data (-) Pin 6 
Black / White 
Activation Sensor COM. 
Orange 
Power input / 12-24 VAC/VDC ( - ) 
Gray 
Bodyguard N.O. Pin 4 
Red / White 
Bodyguard Data (+) Pin 7 & Activation Sensor N.O. 
Brown 
Power input / 12-24 VAC/VDC (+) 
Green 
Door Control Common 
Blue 
Door Control Activation 
Yellow 
Door Control safety 
 
LO-21P WIRING DIAGRAMS: 
 
 
 
 
The wiring shown below may be used on most models of operators. See wiring diagrams at back of this manual for 
specific diagrams. 
 
brown
red/
whi
te
white
gray
purpl
e
orange
24 V 
TRANSFORMER
DATA +  7
DATA -   6
N.C.   5
N.O.  4
COM  3
POWER  2
POWER  1
red
black
blue
green
115 VAC
BODYGUARD
1 2 3 4 5
EAGLE
8  7  6  5  4  3  2  1
Contacts to open 
at desired point of
inhibiting
Approach SuperScan
Stall SuperScan
(Swing Side)
1  2  3  4  5  6  7  8
yellow
SAFETY
AUTO
OFF
HOLD
MOTOR
+
-
OPERATOR
LO-21P
NOTE:
LO-21P DIPSWITCH SETTINGS:
#1 THROUGH #5 - SET FOR
REQUIRED LOCKOUT TIME
#6 ON, #7 OFF, #8 ON
Door Control
COMMON 
ACTIVATION 
STALL 
Blk
/wh
ite
 
 
IMPORTANT: 
Before connecting the red and black wires from the LO-21P to the Motor, be sure to check the polarity of the voltage 
with a multi-meter, to determine which wire is the positive side. The red wire of the lockout module must always be 
connected to the positive side of the motor. When a positive reading is observed on the meter, (while the door is in hold 
open) the red probe indicates the positive side. Thus, the red wire of the lockout will always be attached to whatever 
wire the red probe was on when a positive reading was obtained.  
 
 
NOTES: 
• 
For pairs of doors, wire the additional SuperScans the same as shown above. 
• 
For the inhibit function, operator mounted auxiliary switches may be used – dry contacts only. 
• 
Bodyguard must be programmed to a relay value of 2. 
 
 
NOTE: Bodyguard MUST be programmed 
to a Relay Output value of 2. Default is 1.