Remote Control Connections 
Electrical connections should be made by a qualified ser-
vice technician. Low voltage wires from the remote
controls are connected to the damper motor terminals.
Identify the appropriate installation type and connect as
per illustration.
In order to prevent electric shock when cleaning 
or servicing the HRV, it is extremely important to 
confirm the polarity of the power line that is 
switched by the safety (disconnect) switch. The 
hot line (black) is the proper line to be switched. 
To confirm the proper polarity, use a voltmeter 
or test lamp to ensure there is no power after 
the switch when the door is open. Check 
between that point and ground (on the cabinet).  
Always make sure that the HRV is properly 
grounded.
WARNING
Electrical - Model 94-EXCHANGER-MD ONLY
OPTIONAL
TRANSFORMER
120 VAC
24 VAC
OPTIONAL
TRANSFORMER
120 VAC
OPTIONAL
TRANSFORMER
120 VAC
OPTIONAL RELAY (SPST)
OPTIONAL RELAY (SPST)
On older thermostats, energizing the R and G 
terminals at the forced air system has the effect 
of energizing the Y terminal at the thermostat 
and thereby activating the cooling system. If you 
identify this type of thermostat, you must use 
option 3.
WARNING