Lifebreath RNC120F Benutzerhandbuch

Seite von 28
24
It  is  necessary  to  have  balanced  air  flow  in  an  HRV.  The  volume  of  air
brought in from the outside must equal the volume of air exhausted by
the unit. If the air flow is not properly balanced, then:
The HRV may not operate at its maximum efficiency 
A negative or positive air pressure may occur in the house
The unit may not defrost properly
Failure to balance HRV properly may void warranty
Excessive  negative  pressure may  have  several  undesirable  effects.  In
some  geographic  locations,  soil  gases  such  as  methane  and  radon  gas
may be drawn into the home through basement/ground contact areas. 
Read the Application Warning in Clearances & Requirements section
of this manual!
Prior to balancing, ensure that:
1. All sealing of the duct system has been completed.
2. All of the HRV’s components are in place and 
functioning properly.
3. Balancing dampers are fully open.
4. Unit is on HIGH speed.
5. Air flow in branch lines to specific areas of the house should be
adjusted first prior to balancing the unit. A smoke pencil used at the
grilles is a good indicator of each branch line's relative air flow.
6. After taking readings of both the stale air to the HRV duct and fresh
air to the house duct, the duct with the lower CFM ([L/s] velocity)
reading should be left alone, while the duct with the higher reading
should be dampered back to match the lower reading.
7. Return unit to appropriate fan speed for normal operation
8. A field-supplied balancing damper for the stale air side is required for
system balancing.
Balancing Procedure
The following is a method of field balancing an HRV using a Pitot tube,
which is advantageous in situations when flow stations are not installed
in  the  duct  system.  Procedure  should  be  performed  with  the  HRV  on
high speed.
The first step is to operate all mechanical systems on high speed, which
have an influence on the ventilation system, i.e. the HRV itself and the air
handler,  if  applicable.  This  will  provide  the  maximum  pressure  that  the
HRV will need to overcome, and allow for a more accurate balance of the
unit.
Drill a small hole in the duct (about 3/16"), three feet downstream of any
elbows or bends, and one foot upstream of any elbows or bends. These
are  recommended  distances  but  the  actual  installation  may  limit  the
amount of straight duct.
The  Pitot  tube  should  be  connected  to  a  magnehelic  gauge  or  digital
manometer  capable  of  reading  from  0  to  0.25  in.  (0-62  Pa)  of  water,
preferably to 3 digits of resolution. The tube coming out of the end of the
Pitot is connected to the high pressure side of the gauge. The tube com-
ing  out  of  the  branch  of  the  Pitot  is  connected  to  the  low  pressure  or
reference side of the gauge.
Insert the Pitot tube into the duct; pointing the tip into the air flow.
For general balancing it is sufficient to move the Pitot tube around in the
duct and take an average or typical reading. Repeat this procedure in the
other (supply or return) duct. Determine which duct has the highest air
flow  (highest  reading  on  the  gauge).  Then  damper  that  air  flow  back  to
match  the  lower  reading  from  the  other  duct.  The  flow  should  now  be
balanced.
Actual air flow can be determined from the gauge reading. The value read
on the gauge is called the velocity pressure. The Pitot tube comes with a
chart  that  will  give  the  air  flow  velocity  based  on  the  velocity  pressure
indicated by the gauge. This velocity will be in either feet per minute or
meters per second. To determine the actual air flow, the velocity is multi-
plied by the cross sectional area of the duct being measured.
This is an example for determining the air flow in a 6" duct. 
The Pitot tube reading was 0.025 inches of water.
From the chart, this is 640 feet per minute.
The 6" duct has a cross sectional area of   
= [3.14 x (6"÷12)
2
]÷4
= 0.2 square feet
The air flow is then:
640 ft./min. x 0.2 square feet  = 128 cfm
For your convenience, the cross sectional area of some common round
duct is listed below:
DUCT DIAM. (inches)        CROSS SECTION AREA (sq. ft.)
5
0.14
6
0.20
7
0.27
The accuracy of the air flow reading will be affected by how close to any
elbows  or  bends  the  readings  are  taken.  Accuracy  can  be  increased  by
taking  an  average  of  multiple  readings  as  outlined  in  the  literature  sup-
plied with the Pitot tube. 
Ensure balanced air flow in HRV. Excessive 
positive pressure may drive moist indoor air into 
the external walls of  the building where it may 
condense (in cold weather) and degrade 
structural components. May also cause key 
holes to freeze up. 
CAUTION
Ensure balanced air flow in HRV. Excessive 
negative pressure may also cause the back- 
drafting of vented combustion equipment.
WARNING
Air Flow Balancing