Proper installation/ducting is extremely
important to ensure maximum
performance. Use a qualified and
trained installer.
DUCTING
• Check with a qualified and
trained installer or local codes
for makeup air requirements, if
any.
• Max. duct run length
o For 300 – 1,200 CFM—50’
(152.4 m)
o For 1,500 CFM—75’ (22.9 m)
o For general reference only;
for longer duct runs, increase
duct size and contact a
qualified and trained installer.
o Straight runs and gradual
turns are best; for example,
each 90° elbow is equivalent
to 5’ – 10’ (1.52 – 3.05 cm) of
straight run.
• 7” (17.8 cm) round duct for 
300 – 600 CFM; 10” for 900 –
1500 CFM
o Never use flexible duct; it
creates back pressure/air
turbulence and greatly
reduces performance.
GAS
Not applicable
ELECTRICAL
• Hardwire direct with two-wire
ground
• 120 VAC/60 Hz 
• Max. amp usage (rating
includes recommended
ventilator kit rating)—see
Dimensions & Specifications
table 
PLUMBING
Not applicable
DTWS Slim Traditional
Wall Hood
DTWN Tall 
Traditional Ledgeless
Wall Hood
P L A N N I N G   A N D   D E S I G N   G U I D E
V I K I N G R A N G E . C O M       •       1 - 8 8 8 - V I K I N G 1
R E L E A S E D 1 2 / 1 / 0 7
© 2 0 0 7   V R C — INFORMATION SUBJECT TO CHANGE 
VENTILATION
Designer Built-In Wall Hoods
Installation Requirements
* A 1,200 CFM interior- or exterior-power ventilator should be used when installed over range/rangetop with gas char-grill.
** It is recommended that the 1,500 CFM ventilator be used with longer duct runs.
Note: Maximum amp rating for hoods includes recommended ventilator kit rating. All products must be hard wired with two-wire ground. An interior- or
exterior-power ventilator kit must be purchased for installation with all 18”H. hoods.
Model
Ventilator Kits
Duct Size
Max. Amps   
Interior
Exterior
Interior
Exterior
Interior
Exterior
DTWS3049
DIV300/440
DEV900
7” (17.8 cm)
10” (25.4 cm)
1.7/3.2
6.6
DTWS3649
DIV300/440
DEV900
7” (17.8 cm)
10” (25.4 cm)
1.7/3.2
6.6
DTWS4249
DIV440
DEV900
7” (17.8 cm)
10” (25.4 cm)
3.2
6.6
DTWS4849
DIV880
DEV1200/1500**
10” (25.4 cm)
10” (25.4 cm)
5.6
4.3/5.1
DTWN3048
VIV300/600/1200*
VEV900/1200*
7” (17.8 cm)
10” (25.4 cm)
2.4/4.6/6.6
6.6/3.9
DTWN3648
VIV300/600/1200*
VEV900/1200*
7” (17.8 cm)
10” (25.4 cm)
2.4/4.6/6.6
6.6/3.9
DTWN4248
VIV600/1200*
VEV900/1200*
7” (17.8 cm)
10” (25.4 cm)
4.6/6.6
6.6/3.9
DTWN4848
VIV1200*
VEV1200/1500**
10” (25.4 cm)
10” (25.4 cm)
7.0
4.3/5.1
Note: All CFMs are based on tests with 0.1 static pressure. Without applying static pressure (some brands do not), CFM could be greatly
overstated.