FIELD CONTROLS SWG Stainless Benutzerhandbuch

Seite von 12
SIDEWALL POWER VENTER KIT  
Model: SWG, SWGII & SWG Stainless Series 
*Patented 
TYPICAL VENTING SYSTEM COMPONENTS 
1 - SWG Series Power Venter 
1 - CK Series Control Kit (sold separately) 
OPTIONAL SYSTEM COMPONENTS 
SWG S
ERIES 
T
HROUGH
-W
ALL 
E
XTENSION 
K
IT
 
For installation in wall thickness over 8 inches. Models PEK-4 through PEK-8 are available. 
F
OR 
M
OST 
M
ULTIPLE 
H
EATING 
E
QUIPMENT 
S
YSTEMS
 
One CK Series Control Kit for each appliance. Except for a 24V gas furnace or boiler and a 
30mV water heater multiple venting system, use the CK-90 Series Control Kit. 
CONTENTS 
Available Control Kits .................................... 2 
Maintenance ............................................. 8 
Installation Instructions ................................. 2 
General Inspection ................................... 8 
Wiring............................................................ 7 
Repair Parts.............................................. 9 
Air Flow Adjustments .................................... 7 
System Information ................................ 11 
GENERAL SYSTEM INFORMATION 
Designed for operation with natural gas, LP gas and #2 fuel oil appliances. 
1.  The thermostat (wall thermostat or aquastat) calls for heat and energizes a relay which activates 
the power venter. After the venter motor has come up to speed, the pressure switch closes. This 
closes the circuit to the burner and allows the burner to fire. 
2.  For millivolt controlled water heaters using the CK-20 Series Control Kit, the gas valve pressure 
switch activates the power venter at the same time as the burner fires. 
3.  After the heating requirement has been satisfied, the thermostat circuit will open and de-activate 
the burner and power venter circuit. 
4.  For venting systems equipped with a post purge device, the power venter operates for a period 
of time after the burner has shut off to purge remaining flue gases. 