INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Greenheck Model TAUD, TAUB-CA and TAUB fans are thoroughly inspected and test run at the factory, however damage may 
occur during handling and shipping. Consequently, it is important that the unit be carefully inspected for visible and concealed 
damage before beginning installation. Report any damage to the shipper immediately. In addition, assure all accessory items 
are present.
INSTALLATION
LIFTING - 
Attach a suitable chain or strap to the points depicted in 
Fig. 1. The fan should never be lifted by the motor, tie down points, belt 
tube, damper frame, windband or accessories.
Carefully lift the fan to the roof curb and install fasteners in all holes 
provided in the unit base. The windband need not be removed for the 
lifting operation.
ELECTRICAL CONNECTIONS - 
The electrical supply must be 
compatible with the fan motor voltage, phase and amperage capacity. 
The electrical supply line must be properly fused and conform to local 
and national electrical codes.
For direct drive units, the electrical supply may be routed internally 
and exit through a hole provided in the fan housing if an optional service 
disconnect switch is provided.
For belt drive units, the electrical supply line may be routed internally 
and exit the fan housing through a hole provided below the belt tube 
opening. The electrical supply line should then be either: (1) connected 
to an optional service disconnect switch, or (2) wired directly to the 
motor.
For belt drive units in continuous high temperature installations, 
the electrical supply must be kept out of the airstream. This means 
bringing the supply lines off the roof deck not through the fan. The 
electrical supply line should then be either: (1) connected to an optional 
service disconnect switch, or (2) wired directly to the motor.
For belt drive units in emergency smoke removal installations, the electrical supply must be kept out of the airstream. 
They may also require an isolated power supply so that if power is cut to the building in the event of a fire, the fan will continue 
to operate. Check the local and national electrical codes for emergency smoke removal fans.
READ AND SAVE THESE INSTRUCTIONS
TUBE AXIAL UPBLAST FANS
Model TAUD (Direct Drive, Aluminum Propeller)
Model TAUB-CA (Belt Drive, Aluminum Propeller)
Model TAUB (Belt Drive, Steel Propeller, High Temp.)
 Part # 453905
** WARNING **
Disconnect and secure to the “off” position all electrical power to the fan prior to inspection or 
service.
Caution must be used when working around the fusible link damper lifters. They contain preloaded 
springs and may open the dampers unexpectedly.
Models TAUD and TAUB-CA may have fusible link damper lifters. All model TAUB units designed 
for emergency smoke operation have fusible link damper lifters. TAUB fans UL listed as “Power 
ventilators for smoke control systems” in sizes 42, 48, 54 and 60 have extra heavy duty fusible 
link damper lifters under high spring tension that, for safety reasons, must be pinned to prevent 
accidental release during inspection or service. See page 2 for details on how to secure the lifter 
arms.
FAILURE TO COMPLY WITH THESE SAFETY PRECAUTIONS MAY 
RESULT IN SERIOUS INJURY OR DEATH!
®
 Fig. 1  Lifting Point
(4 places)