Seite von 6
Model SMD-301V meets the requirements for smoke 
dampers established by:
National Fire Protection Association 
    NFPA Standards 92A, 92B, 101 & 105
IBC International Building Codes
New York City (MEA listing #260-91-M)
CSFM California State Fire Marshal 
  Leakage (Smoke) Damper Listing (#3230-0981:104)
Application
Model SMD-301V is a vertical blade low leakage rated smoke 
damper. High strength airfoil blades insure lowest resistance to 
airflow in HVAC systems with velocities to 4000 fpm (20.3m/s) and 
4 in. wg (1.0 kPa).
UL555S Leakage Rating
 
Leakage Class:  
Operational Rating 
 
Maximum Velocity: 
2000 fpm (20.3 m/s) up to 
 
 
100 in. x 32 in. H 
 
 
(2540mm x 813mm) or 
 
 
4000 fpm  (20.3 m/s) up to 
 
 
50 in. x 32 in. (1270mm x 813mm) 
 
Maximum Pressure:  
4 in. wg (1 kPa) 
 Maximum Temperature: 
350ºF (177ºC)
Standard Construction
 
Frame:  
5 in. x 1 in. (127mm x 25mm) 
 
 
galvanized steel hat channel with 
 
 
reinforced corners. A low profile 
 
 
head and sill are used on sizes 
 
 
less than 17 in. (432mm) high to 
 
 
maximize free area and 
 
 
performance. 
 
Blades:  
Double skin airfoil shape of 
 
 
galvanized steel with full length 
 
 
structural reinforcement. 14 ga. 
 
 
(2 mm) equivalent thickness. 
 
Seals: 
Extruded silicone rubber blade 
 
 
seals.  Flexible stainless steel 
 
 
jamb seals. 
 
Linkage: 
Concealed in jamb. 
 
Axles: 
1
/
2
 in. (13mm) dia. plated steel. 
 
Bearings: 
304 stainless steel
Size Limitations:
 
Minimum Size: 
6 in. W x 8 in. H 
 
 
(152mm  W x 203mm H) 
 
Maximum Size: 
 
Single Section: 
50 in. W x 32 in. H 
 
 
(1270mm W x 813mm H) 
 
Multiple Section: 
100 in. W x 32 in. H 
 
 
(2540mm W x 813mm H)
Optional Features:
• OCI (Open closed indication switches)
•  Electric or pneumatic actuators to accomplish smoke 
management and system functions.
• Transitions (R, C, O)
• POC retaining angles
• Momentary Switch
• Sealed transitions and sleeves
Model SMD-301V
Smoke Dampers
Steel Airfoil Blades
UL 555S Leakage Class I
*W&H dimensions furnished approximately 
1
/
4
 in. (6mm) undersize.
“UL CLASSIFIED (see complete marking on 
product)”
“UL CLASSIFIED to Canadian safety standards 
(see complete marking on product)”
 
Standard 555S (Listing #R13317)
W*
H*
Installation instructions available at www.greenheck.com