Greenheck Fan BDF Benutzerhandbuch

Seite von 8
1
Model BDF • Belt Drive Duct Fan
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting 
to assemble, install, operate or maintain the product described. Protect yourself and others by 
observing all safety information. Failure to comply with instructions could result in personal injury 
and/or property damage!
®
PN 458341
Model BDF 
Belt Drive Duct Fan
DANGER
Always disconnect, lock and tag power source before 
installing or servicing. Failure to disconnect  power 
source can result in fire, shock or serious injury.
CAUTION
When servicing the fan, motor may be hot enough 
to cause pain or injury. Allow motor to cool before 
servicing.
CAUTION
Precaution should be taken in explosive 
atmospheres.
General Safety Information
Only qualified personnel should install this fan. 
Personnel should have a clear understanding of 
these instructions and should be aware of general 
safety precautions. Improper installation can result 
in electric shock, possible injury due to coming in 
contact with moving parts, as well as other potential 
hazards. Other considerations may be required if 
seismic activity is present. If more information is 
needed, contact a licensed professional engineer 
before moving forward.
  1.  Follow all local electrical and safety codes, as 
well as the National Electrical Code (NEC) and 
the National Fire Protection Agency (NFPA), 
where applicable. Follow the Canadian Electric 
Code (CEC) in Canada.
  2.  The rotation of the wheel is critical. It must be 
free to rotate without striking or rubbing any 
stationary objects.
  3.  Motor must be securely and adequately 
grounded.
  4.  Do not spin fan wheel faster than max cataloged 
fan RPM. Adjustments to fan speed significantly 
effects motor load. If the fan RPM is changed, 
the motor current should be checked to make 
sure it is not exceeding the motor nameplate 
amps.
  5.  Do not allow the power cable to kink or come 
in contact with oil, grease, hot surfaces 
or chemicals. Replace cord immediately if 
damaged.
  6.  Verify that the power source is compatible with 
the equipment.
  7.  Never open access doors to a duct while the fan 
is running.
Model BDF
Belt Drive Duct Fan
Model BDF is a belt drive duct supply, exhaust or return air fan. These 
fans  are  specifically  designed  for  inline  applications.  Performance 
capabilities range up to 15,000 cfm (25,500 m
3
/hr) and up to 3.0 in. wg 
(747 Pa) of static pressure. BDF fans are available in seven sizes with 
nominal wheel diameter ranging from 8 to 20 inches (203 to 508 mm) 
(080 - 200 unit sizes).  Each  fan  shall  bear  a  permanently  affixed 
manufacture’s  engraved  metal  nameplate  containing  the  model 
number and individual serial number.