Greenheck Fan DFD-XXX Merkblatt

Seite von 1
These instructions apply to 11/2 hour rated combination fire smoke 
dampers and curtain fire dampers mounted horizontally in concrete 
floors. Specific requirements in these instruction are mandatory. These 
instructions meet the requirements of UL 555. Installation shall comply 
with the requirements of NFPA 90A (Standard for the Installation of Air 
Conditioning and Ventilating Systems) and UL Classification R13317.
Dampers up to a maximum size of 144 in. W x 96 in. H (3658mm x 2438mm) may be installed as illustrated 
below.
Fire damper and sleeve assemblies 144 in. W x 96 in. H (3658mm x 2438mm) and smaller only require 
retaining angles on top of the concrete floor. Retaining angles must be installed on top of the floor and attached to the sleeve 
and the floor.
Retaining angles must be attached to the sleeve.
• Retaining angles must be a minimum of 16 gauge (1.5mm) steel and have a minimum of 11/2 in. x 11/2 in. 
(38mm x 38mm) legs.
• Retaining angles must be attached to the sleeve using one of the methods shown below:
•  tack or spot welds
•  #10 sheet metal screws or 1/4 in. nuts and bolts
•Retaining angles must be attached to the concrete floor using the method shown below:
•  Steel anchors or self tapping concrete screws penetrating concrete floor a minimum of 11/4 in. (32mm)
• A minimum of two connections per side with a maximum spacing of 6 in. (152mm) on center
• Retaining angles must overlap the floor a minimum of 1 in. (25mm)
Copyright © 2008 Greenheck Fan Corporation
468236 Single Side Retaining Angle-Horizontal 
Mount Rev.3  August 2008
A = Damper
B = Retaining Angle
C = Screws
Part number 468236
INSTALLATION INSTRUCTION SUPPLEMENT
Refer to:
‘Installation Instructions for FD, DFD, SSFD, & KFD Models’
(Part #452763)
or
‘Installation Instructions for FSD-XXX, DFD-XXX, SSFSD-XXX & 
CFSD-XXX Series Fire & Combination Fire Smoke Dampers’ (Part 
#461336)
or
‘Installation Instructions for FD & DFD 150X Series Curtain Fire 
Dampers’ (Part #453946) for additional details.
Single Side Retaining Angle-Horizontal Mount
FD & DFD Series
1
1
/
2
 Hour Fire Dampers
 
and
FSD Series
1
1
/
2
 Hour Combination Fire Smoke 
Dampers-Horizontal Mount
“UL CLASSIFIED 
(see complete marking on product)”
“UL CLASSIFIED to Canadian safety standards                   
(see complete marking on product)”
 
Standards UL 555 & 555S
Classifications Filed at UL under Listing #R13317
CONCRETE 
FLOOR
DAMPER
 SLEEVE