Quattro DC Motor Side Power Convert A4 Submenu 
 
Motor Side Power Convert A4 submenu 
Parameter Description 
Units 
Default
Range 
Hidden
Item 
Run 
lock
out 
ARM RESISTANCE 
(Armature Circuit Resistance)  
Affects tuning of the armature 
current regulator.  Load this 
parameter with known or 
measured value.  Only used is 
GAIN SELECTION (A4) is set to 
Manual.  
Ohm 
0.5000  0.0001 – 2.9999 
Y N 
ARM INDUCTANCE 
(Armature Circuit Inductance) 
Affects tuning of the armature 
current regulator.  Load this 
parameter with known or 
measured value. Only used is 
GAIN SELECTION (A4) is set to 
Manual. 
mH 
15.00 
0.01 – 327.67 
Y N 
MTR REV VLT LIM 
(Motor Revolution Voltage Limit) 
Determines crossover point 
during regeneration at low speed 
from using CEMF to reverse 
plugging of motor.  If set too high 
there will be a hesitation in 
torque.  If set too low, there may 
be an oscillation squeal heard 
from the motor. 
4.80 
0.01 – 30.00 
Y N 
IF REG INT GAIN 
(Field Current Regulator integral 
Gain)  The integral gain for the 
current regulation of the motor 
field.  Rarely needs to be 
changed from the default.  
none 
0.90 
0.00 – 30.00 
Y N 
IF REG PROP GAIN 
(Field Current Regulator 
Proportional)  The proportional 
gain for the current regulation of 
the motor field. Rarely needs to 
be changed from the default.  
none 
6.07 
0.00 – 16.38 
Y N 
AUTO TUNE MOTOR 
(Auto Tune Motor)  
Begins the procedure to calculate 
motor parameters.  See Auto 
Tune Procedure on page 95. 
none - 
Start Auto 
Tune? 
GAIN SELECTION 
(Gain Selection)   
If set to MANUAL, values in ARM 
RESISTANCE (A4), ARM 
INDUCTANCE (A4), If REG INT 
GAIN (A4), and If REG PROP 
GAIN (A4) will be used.   
If set to AUTOTUNE, the 
armature regulator gains are set 
using AUTO MEAS ARM L(D2) 
and AUTO MEAS ARM R (D2).  
AUTO FLD INT (D2), and AUTO 
FLD PROP (D2) will be used to 
tune the respective regulators. 
none Manual 
− Autotune 
− Manual 
N N 
43