Quattro DC Logic Outputs C3 Submenu 
 
Logic Outputs C3 submenu 
LOGIC OUTPUT x
 
(Logic Outputs 1-4) 
This parameter defines the function of the logic 
outputs.   
NOTE:  The current setting of each parameter 
is displayed in all caps; all other choices in the 
list are displayed in lower case. 
 
RELAY COIL x  
(Relay Logic Outputs 1-2) 
This parameter defines the function of the 
relay logic outputs.   
NOTE:  The current setting of each parameter 
is displayed in all caps; all other choices in the 
list are displayed in lower case.
Parameter 
Description 
  Defaults 
Hidden 
Item 
Run 
lock
out 
LOGIC OUTPUT 1 (TB1-25)
 
logic output #1 
note: drive comes pre-wired for logic 
output #1 to be CLOSE CONTACT 
CLOSE CONTACT 
LOGIC OUTPUT 2 (TB1-26)
 
logic output #2 
RUN COMMANDED 
LOGIC OUTPUT 3 (TB1-27)
 
logic output #3 
MTR OVERLOAD 
LOGIC OUTPUT 4 (TB1-28)
 
logic output #4 
ENCODER FLT 
LOGIC OUTPUT 5 (TB1-29) 
logic output #5 
FAULT 
LOGIC OUTPUT 6 (TB1-30) 
logic output #6 
SPEED REG RLS 
LOGIC OUTPUT 7 (TB1-31) 
logic output #7 
SPEED REG RLS 
RELAY COIL 1 (TB1-21/22)
 
relay output #1 
NO FUNCTION 
RELAY COIL 2 (TB1-23/24)
 
relay output #2 
NO FUNCTION 
SSR1 (TB1-1/3/5) 
solid State Relay 1 
NO FUNCTION 
SSR2 (TB1-8/10/12) 
solid State Relay 2 
NO FUNCTION 
 
choices
 
alarm 
(Alarm) The output is true when an alarm is declared by the drive.
 
 
alarm+flt 
(Alarm and/or Fault) The output is true when a fault and/or an alarm is declared by the drive.  
auto brake 
(Auto Brake) The output is controlled by the Auto Brake function and is used to open the 
mechanical brake. (only multi-step speed commands)  
brake hold 
(Brake Hold) The output is true when the brake pick confirmation is received.  It is used to 
show the mechanical brake is remaining open.  This function is used with brakes that need to 
have less than 100% voltage to hold the brake open.  
brake pick 
(Brake Pick) The output is true when the speed regulator is released and is used to open the 
mechanical brake.  
brk hold flt 
(Brake Hold Fault) The output is true when the brake hold command and the brake feedback 
do not match for the user specified time.  
brk pick flt 
(
Brake Pick Fault) The output is true when the brake pick command and the brake feedback do 
not match for the user specified time.  
car going dwn 
(Car Going Down) The output is true when the motor moves in negative direction faster than 
the user specified speed.   
car going up 
(Car Going Up) The output is true when motor moves in positive direction faster than user 
specified speed.  
charge fault 
(Charging Fault) 
The output is true when the DC bus voltage has not stabilized above the voltage fault level or 
the charge contactor has not closed after charging.  
close contact 
(Close Motor Contactor) The output is true when the run command is given, the drive is 
enabled, the software has initialized, and no faults are present.  
contactor flt 
(Contactor Fault) The output is true when the command to close the contactor and the 
contactor feedback do not match before the user specified time.  
curr reg flt 
(Current Regulator Fault) The output is true when the actual current measurement does not 
match commanded current.  
drv overload 
(Drive Overload) The output is true when the drive has exceeded the drive overload curve.  
encoder flt 
(Encoder Fault) The output is true when the encoder is disconnected or not functioning, while 
attempting to run 
fault 
(Fault) The output is true when a fault is declared by the drive.  
flux confirm 
(Motor Flux Confirmation) The output is true when the drive has confirmed there is enough 
motor field current (flux) to issue a speed regulator release.  Threshold is set by measured 
motor field current being greater than that set at Motor parameter A6, Flux Confirm Level.  
63