Quattro DC Troubleshooting 
 
Name Description 
Possible Causes & Corrective Action 
Undervolt Flt 
 
Generated during a run 
condition when the DC bus 
voltage drops below the user 
specified percent of the DC 
link voltage.  The fault level is 
specified by the UV Fault 
Level parameter.  
Low Input Voltage 
 
Check INPUT L-L VOLTS (A5) and UV FAULT 
LEVEL (A4) 
 
Verify proper input voltage and increase, if 
necessary, the input AC voltage within the 
proper range 
 
Check for missing input phase 
 
Check power line disturbances due to starting 
of other equipment 
Drive Accurately Reading the DC Bus 
 
Measure the DC bus with a meter  
 
Compare that with the value on the digital 
operator, BUS VOLTAGE (D2) 
Poor Tuning of Line Side Parameters 
 
Check DC BUS REG P GN (A5), DC BUS 
REG I GN (A5), DC BUS V BOOST (A5), and 
BUS VREF SOURCE (A5) 
Line Converter Problem 
 
Verify the line converter did not shutdown 
while the motor controller was in process of 
regeneration 
UV Alarm 
 
(alarm) 
Generated during a run 
condition when the DC bus 
voltage drops below the user 
specified percent of the dc link 
voltage.  The fault level is 
specified by the UV Alarm 
Level parameter.  
Low Input Voltage 
 
Check INPUT L-L VOLTS (A5) and UV 
ALARM LEVEL (A4) 
 
Verify proper input voltage and increase, if 
necessary, the input AC voltage within the 
proper range 
 
Check for missing input phase 
 
Check power line disturbances due to starting 
of other equipment 
Drive Accurately Reading the DC Bus 
 
Measure the DC bus with a meter  
 
Compare that with the value on the digital 
operator, BUS VOLTAGE (D2) 
Poor Tuning of Line Side Parameters 
 
Check DC BUS REG P GN (A5), DC BUS REG 
I GN (A5), DC BUS V BOOST (A5), and BUS 
VREF SOURCE (A5) 
Table 1 : Troubleshooting Guide