GP Series Portable Chillers 
Chapter 2: Functional Description 
10 of 90 
differential” value the controller will enable the compressor; if equipped with two 
compressors the controller will enable the one with the least amount of hours.  The second 
compressor will be enabled if the leaving fluid temperature remains above the setpoint plus 
the “compressor on differential” value for more than 60 seconds. 
The hot gas valve is designed to trim the load of one compressor and will modulate in order 
to meet the desired leaving fluid setpoint via a PID algorithm.  After the compressor starts, 
the hot gas valve is allowed to modulate.  The compressor will shut off if the leaving fluid 
temperature drops below the “compressor off differential” and the hot gas valve is at 100% 
for the “compressor off delay” time. The hot gas will reset to 0% when the compressor is off.  
There is a “compressor anticyle” timer that will delay the time between compressor starts to 
prevent short cycling of the compressor.  This is a start to start timer set at 5 minutes.  For 
example, if the compressor has been running for 5 minutes and shuts off, then the compressor 
can start immediately if the demand is there.  If it has only been running for 2 minutes, then it 
would not be able to start again for 3 minutes. 
For a unit with two compressors, the second compressor or lag compressor starts when the 
lead compressor is on, the hot gas is at 0%, and the leaving fluid temperature is above the 
setpoint plus the “compressor on differential”.  There is also an adjustable “lag compressor on 
delay” timer.  Before starting either compressor, the compressor with the least amount of 
runtime hours is considered the lead compressor and the first to start.  When both 
compressors are running, the compressor with the most hours is considered the lead 
compressor and is the first to stop.  The lead compressor will shut off if the leaving fluid 
temperature drops below the “compressor off differential” and the hot gas valve is at 100% 
for the “lead compressor off delay” time.  The compressor anti-cycle timers are active with 
the two compressor units. 
There will be two PID controls running simultaneously for determining the position of the hot 
gas valve.  One PID output will be based on leaving fluid temperature and the other based on 
a minimum saturated suction temperature for freeze protection.  The hot gas valve position 
will be determined by which output is greater.  If it is controlling to the saturated suction 
temperature to prevent freezing, a warning will display on the screen that the hot gas is in this 
mode.  Once the control goes back to setpoint control, the warning will disappear.  The 
saturated suction temperature is calculated from the suction pressure and the type of 
refrigerant. 
The discharge pressure is controlled using an analog output signal to drive a fan for air-
cooled units or a water regulating valve for water-cooled units.  The output signal is 
determined from a PID algorithm using a discharge pressure transducer as the process 
variable.  The VFD or water regulating valve is controlled from the analog output to an 
adjustable discharge pressure setpoint.  The analog output starts at the initial “discharge 
pressure start” % for a given time delay (discharge pressure hold).  After the time delay, it 
will control to the discharge pressure setpoint via the PID control.  There is also a setting to 
control the discharge pressure to the most efficient value. 
2-3  Standard Features 
Mechanical Features 
Compressor – Hermetic scroll compressors. 
Evaporator – Stainless steel copper brazed plate evaporators.