Chapter 3: Installation 
27 of 90 
 
Figure 9: Double Riser Detail 
3-8  Checking Motor Direction 
All of our portable chillers have their motor rotations properly phased at the factory. If 
compressors, pumps, or fans are running in reverse rotation, disconnect and lock out the 
power source and reverse any two power leads into the chiller disconnect switch.   
Caution!  Do not switch leads at the motors, motor starters, or contactors. 
Three-Phase Compressors 
Scroll compressors are directionally-dependent and compress in one rotational direction. 
Reversing rotation direction results in an elevated sound level and a substantially-reduced 
current draw. 
Caution!  Do not allow the compressor to run backwards for any length of time.  Doing 
so will result in compressor damage.. 
Water Pumps 
Correct pump rotation is indicated by a positive pressure of 20 to 40 psi shown on the home 
screen of the display. Pump rotation should be clockwise when viewed from the motor end. 
For chillers with optional pumps, check the appropriate pump curve in the Appendix. 
Caution!  Do not run pump dry. Doing so will result in seal damage. 
Condenser Fan 
Air should be drawn through the condenser and discharged vertically from the chiller.