Chapter 4: Operation 
41 of 90 
 
4-4  Access Levels 
The controller is setup to allow access to three distinct password groups: operator, supervisor, 
and service.  Operator access allows the user to modify the Leaving Water Temp, Hi Temp 
Warning, and Hi Temp Fault setpoints. Supervisor access allows the supervisor to modify the 
above plus  
Selecting any of the menus in the Menu Screen will display the Password Screen. 
 
 
4-5  Controller Setpoints 
 
Variable 
Description 
Access Level 
Operator 
Supervisor 
Chilled Fluid SP 
Temperature of chilled fluid out to process 
Chil Hi Temp Wrn 
Setpoint for alarm to warn when chilled leaving fluid 
temperature is too high 
Chil Hi Temp Flt 
Setpoint to shut down pump and compressor based 
on leaving fluid temperature 
Process SP 
Temperature of tempered fluid out to process 
Proc Hi Temp Wrn 
Setpoint for alarm to warn when tempered leaving 
fluid temperature is too high 
Proc Hi Temp Flt 
Setpoint for alarm to warn when tempered leaving 
fluid temperature is too high 
Proc Low Temp Wrn 
Setpoint for alarm to warn when tempered leaving 
fluid temperature is too low 
Proc Low Temp Flt 
Setpoint for alarm to warn when tempered leaving 
fluid temperature is too low 
Cooling Enabled 
Refrigeration system allowed to operate 
 
Heating Enabled 
Optional Process temperature heater allowed to 
operate 
 
Fluid Freeze Point 
Lowest temperature fluid will operate without 
freezing.  Below 32°F (0°C) glycol must be added.  
Forces lowest Chilled fluid setpoint to be 13°F (7°C) 
above FFP 
 
Chill On Diff 
Temperature difference above chilled fluid setpoint 
before compressor turns on 
 
Chill Off Diff 
Temperature difference below chilled fluid setpoint 
before compressor turns off 
 
Proc On Diff 
Temperature difference below process setpoint 
before process heater turns on 
 
Proc Off Diff 
Temperature difference above process setpoint 
before process heater turns off 
 
Proc Hi Temp Dly 
Time (in seconds) Process High Temperature alarm 
is ignored before activating