LEGEND 
 
 
C.B. 
CIRCUIT BREAKER 
D.E. 
DUAL ELEMENT FUSE 
DISC SW 
DISCONNECT SWITCH 
FACT CB 
FACTORY-MOUNTED CIRCUIT BREAKER 
FLA 
FULL LOAD AMPS
HZ 
HERTZ
MAX 
MAXIMUM
MCA 
MINIMUM CIRCUIT AMPACITY
MIN 
MINIMUM
MIN NF 
MINIMUM NON-FUSED
RLA 
RATED LOAD AMPS
S.P. WIRE 
SINGLE-POINT WIRING
Electrical Notes
NOTES:
 1.  U.L. Label is provided on 50 and 60 Hz units for these electrical wiring configurations.
2.  ––  ––  ––  ––  ––  ––  Dashed Line = Field Provided Wiring.
3.  The above recommendations are based on the National Electric Code and using copper conductors only. Field wiring must also comply 
with local codes. Group Rated breaker must be HACR type for cUL machines.  
1.   As standard, all units have single point power connection.  Contact factory for information regarding dual 
point power units.
2.   Maximum Inverse Time Circuit Breaker or Dual Element Fuse - 225% of the largest compressor RLA 
plus the sum of all other loads per NEC 440.22 (A). 
3.   MCA - Minimum Circuit Ampacity  - 125% of the largest compressor RLA plus 100% of the remaining 
compressor RLA's plus the sum of all condenser fan FLA's per NEC 440.33
4.   Recommended time delay or dual element fuse size  - 150%of the largest compressor RLA plus 100% 
of the remaining compressor RLA's plus the sum of all condenser fan FLA's.
5.   RLA   - Rated Load Amps - rated in accordance with UL standard 1995.
6.   Local codes may take precedence.
7.   Control KVA includes operational controls and evaporator heaters.
8.   System inrush current is less than RLA due to the use of York Variable Speed Drive technology. Typical 
Compressor Starting Current ( first four seconds of startup):
Rated Voltage                 Typical Starting Current per Compressor
 
 
       380-400/50/3 
 
 
 
28A
 
 
          380/60/3   
 
 
 
29A
                                    460/60/3   
 
 
 
23A
9.   Voltage Utilization Range:
 
 
      Rated Voltage 
 
 
Utilization Range
 
 
      380-415/50/3 
 
 
    360 - 440
 
 
         380/60/3   
 
 
    342 - 402
 
 
         460/60/3   
 
 
    414 - 508