Press the up ▲
▲ key to begin calibrating.
The controller displays the name of the current calibration
(examples: 32 SC.L; 32 rC.L; 510 SC.H; or 510 rC.H).
(examples: 32 SC.L; 32 rC.L; 510 SC.H; or 510 rC.H).
Wait until the control displays “don” or “bad.”
A “don” message in the Setpoint display indicates the cali-
bration was successful. A “bad” message in the Setpoint
display indicates a bad calibration.
bration was successful. A “bad” message in the Setpoint
display indicates a bad calibration.
Press Select to start the next calibration.
Pressing and releasing the Select key at the end of a
calibration tells the controller to perform the next calibra-
tion.
calibration tells the controller to perform the next calibra-
tion.
Exit Calibration Mode.
Press and hold the Select key for 3 seconds to exit the
Calibration Mode.
Calibration Mode.
You can now proceed to the next test in Test Mode, or
disable Test Mode and resume normal operation.
disable Test Mode and resume normal operation.
C
ALIBRATING
T
EMPERATURE
S
ENSORS
UGH004/0999
microKool Portable Chillers
M
AINTENANCE
5-13
6
7
NOTE: The original calibration value stored in
EEProm can be restored for the current calibration
by pressing the STOP key at any time.
EEProm can be restored for the current calibration
by pressing the STOP key at any time.
8
9