CONDENSER FREEZE POINT, then the CONDENSER WATER PUMP shall be energized 
until the 
CONDENSER REFRIG TEMP is greater than the CONDENSER FREEZE POINT plus 
5° F (2.7° C). An alarm will be generated if the machine is in 
PUMPDOWN mode and the pump 
is energized. An alert will be generated if the machine is not in 
PUMPDOWN mode and the 
pump is energized. If in recycle shutdown, the mode shall transition to a non-recycle shutdown.
Tower-Fan Relay
This control can be used to assist the condenser water temperature control system (field 
supplied). Low condenser water temperature can cause the chiller to shut down on low 
refrigerant temperature. The tower fan relay, located in the starter, is controlled by the PIC to 
energize and deenergize as the pressure differential between cooler and condenser vessels 
changes in order to prevent low condenser water temperature and to maximize machine 
efficiency. The tower-fan relay can only accomplish this if the relay has been added to the 
cooling tower temperature controller. The 
TOWER FAN RELAY is turned on whenever the 
CONDENSER WATER PUMP is running, flow is verified, and the difference between cooler 
and condenser pressure is more than 30 psid (207 kPad) or entering condenser water 
temperature is greater than 85 F (29 C). The 
TOWER FAN RELAY is deenergized when the 
condenser pump is off, flow is lost, the evaporator refrigerant temperature is less than the 
override temperature, or the differential pressure is less than 28 psid (193 kPad) and entering 
condensing water is less than 80 F (27 C).