Siemens FX300 Benutzerhandbuch

Seite von 80
3
 INSTALLATION 
26 
SITRANS FX300
www.siemens.com/flow
06/2009 - SFIDK.PS.050.F2.02   A5E02100423
3.5  Inlet and outlet runs
3.5.1  Minimum inlet runs
1  General inlet run without disturbing flow ≥ 20 DN
2  Behind a control valve ≥ 50 DN
3  After a pipe diameter reduction ≥ 20 DN
1  After a single bend 90° ≥ 20 DN
2  After a double bend 2x90° ≥ 30 DN
3  After a double three-dimensional bend 2x90° ≥ 40 DN