ERROR CODES FOR ON-BOARD DISPLAY
The DFS-1 has a single-digit alphanumeric display to show error codes when something is wrong. Following is a
list of the meanings of the numbers in that display:
0
All conditions nominal
1
Undervoltage trip ................................................. Line voltage dropped below minimum level
2
Overvoltage trip of drive ...................................... Bus voltage exceeded safe limit
3
Undervoltage timer tripped .................................. Line voltage low for too long
4
Instantaneous overcurrent .................................... Excessive transistor current
5
Loss of encoder signal .......................................... Encoder speed signals lost.
Encoder loss detection applies only when pulse
multiplier is set to 4X
6
Motor thermal tripped .......................................... Motor is too hot or thermal is disconnected
7
Commutation fault ............................................... Signals from position encoder lost
8
+24VDC lost at TB2-A14 and TB2-B1 ............... Fuse FR1 overloaded
9
+24VDC lost at TB3-B1 ...................................... Fuse FR2 overloaded
A
+5VDC lost at TB1-A8 ........................................ Fuse FR4 overloaded
B
+24VDC lost at TB1-A10 .................................... Fuse FR3 overloaded
C
Current limit ......................................................... Drive is at maximum current output
D
Timed Overload.................................................... Timed overcurrent has occured
E
Display fault ......................................................... Fault in display module
F
Applications fault ................................................. Fault in applications program
5.0  DFS - 1  ERROR CODES