EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL
12–89
EPM 5300 Series Meters
Chapter 12: Groups 4, 5 and 6—
Set Limits and 
Relays
GE Consumer & Industrial
Multilin
Groups 4, 5 and 6—Set Limits and Relays
The EPM 5300P -NL offers a comprehensive limit and set point functionality.  The user can 
program above or below limits for every reading, including %THD. When a voltage or 
current measurement exceeds a particular value, the set limit is triggered and alerts the 
user. Each limit can trigger two internal Form C dry contact relays for alarm or secondary 
protection. 
The EPM 5300P offers two set limit points available for each measured function: LM1 and 
LM2. Each limit can be set at any desired level. Note: The EPM 5200P does not have limit 
setting capability.
FIGURE 12–1: Example of LM1/LM2 Set Limits
LM1 AND LM2 SET LIMITS
PHASES
CURRENT
0
20
40
60
80
100
120
A
B
C
120
40
LM1 is triggered
LM2 is triggered
50
(AMPS)
80
LM1 SET TO
TRIGGER ABOVE
100 AMPS.
LM2 SET TO
TRIGGER BELOW
50 AMPS.