EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL
LIMITS OR RELAYS PROGRAMMING PROCEDURE
CHAPTER 12: GROUPS 4, 5 AND 6—SET LIMITS AND RELAYS
12.8 Limits or Relays Programming Procedure
Note
The procedure for programming any limit or relay for each group is identical.  The example 
below signifies the exact procedure for programming a Limit/Relay for GROUPS 4–6.
—Group 4 is used as an example.
Note
Press MAX/MIN/LIMITS at any time to cancel before storing the last digit or switch.
Step 1:
a. Enter Group Level of Programming Mode 
     (see Chp. 8).
b. Press MAX/MIN/LIMITS until 4. appears in upper  
     display.
c. Press AMPS to activate the Group.
Step 2:
a. Press MAX/MIN/LIMITS to select desired Function. 
 Middle display provides the currently selected value for 
whether to trip above or below, activate Relay 1 and 
activate Relay 2. 
Left Switch:  UP position indicates above tripping  value 
for lower display’s value.  DOWN position indicates below 
tripping.
Middle Switch:  UP position sets Relay 1 to trip.  
DOWN position doesn’t activate Relay 1 when limit  
condition exists.
Right Switch:  Same as Middle Switch , regarding Relay 2.
  b. Press VOLTS to toggle between LM1 and LM2 settings.  
 The LM1 or LM2 annunciator indicates the limit being 
displayed.
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWH
KVAH
AC VOLTS
AC AMPS
POWER
N
C
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS AMPS
POWER
GROUP
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWH
KVAH
AC VOLTS
AC AMPS
POWER
N
C
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS AMPS
POWER
FUNCTION
RELAY
LIMIT
SWITCHES
VALUE